0 diagnostics, verification, and troubleshooting – Vanguard EZCT-2000C Plus User Manual

Page 106

Advertising
background image

EZCT-2000C USER’S MANUAL

REV 1

102

5.0 DIAGNOSTICS, VERIFICATION, AND TROUBLESHOOTING

5.1

Performing a Diagnostics Test

The Diagnostics test mode displays the output voltage at the selected X leads (V

x

), the voltage

sensed by the H leads (V

h

), and the X voltage excitation current (I

x

). These values can then be

verified using an external volt meter and ampere meter.

To perform a diagnostic test:

a. Start from the “START-UP” menu:

Press the

[4]

key (DIAGNOSTICS).

b. The following screen will be displayed:

Select the tap connection by pressing the corresponding key (

[1]

[4]

). If the tap

connection is not listed, press the

[5]

key to view the next page of options and then

select the correct tap connection.

c. The following screen will be displayed:

Select the maximum output voltage on the X terminals by pressing the corresponding
key (

[1]

[5]

).

select voltage range
1.

50v

2.

300v

3.

500v

4.

1200v

5.

2000v

select tap
1.

x1-x2

2.

x1-x3

3.

x1-x4

4.

x1-x5

5.

next page

1.

RUN TEST 05/07/13

2.

SETUP 08:18:28

3.

TEST PLANS

4.

DIAGNOSTICS

5.

CURRENT SOURCE