TRM-20 AND TRM-40 USER’S MANUAL

REV 1

58

3.14 Demagnetizing the Transformer Core

You can demagnetize the transformer core using the steps below:

a. Start from the “Start-Up” menu:

Press the

[1]

key (RUN TEST

b. The following screen will be displayed:

Press the

[4]

key (DEGAUSS WINDING).

c. The following screen will be displayed:

Select the degaussing current by pressing the corresponding key on the alpha-numeric
keypad.

d. The following screen will be displayed:

Press the

[ENTER]

key to continue.

THIS MAY TAKE SEVERAL
MINUTES TO COMPLETE

"ENTER" to continue


DEGAUSS CURRENT:
1. 0.5 AMP
2. 1 AMP
3. 2 AMPS
4. 5 AMPS
5. 10 AMPS

1. RESISTANCE TEST
2. SPECIAL RES TEST
3. DYNAMIC LTC TEST
4. DEGAUSS WINDING


1. RUN TEST
2. SETUP
3. USER DIAGNOSTICS