Alternate/Simultaneous Operation –

Two Wire Mode, Sinking Type Input

Devices

1. Refer to Figures 17a through 20a for various

switching devices which can be used.

2. Jumper the positive (+) inputs of the

opto- coupler Terminal Block TB-1,
Terminals 1, 3, and 5 together. Tighten
Terminals 1 and 3 securely.

3. Connect a DC power source, positive (+)

voltage to Terminal 5, TB-1.

a. Positive (+) DC if external power supply

is used or, Tighten Terminal 5 securely.

or,

b. Jumper from Terminal 7 of Terminal

Block TB-1 to Terminal 5 if internal
voltage source is used. Tighten both
Terminals 5 and 7 of Terminal Block
TB-1 securely.

4. Connect a DC power source, negative (-)

voltage to Terminal 2, TB-1.

a. Negative (-) DC of external power supply

used. Tighten Terminal 2 securely.

b. Jumper from Terminal 8 of Terminal

Block TB-1 to Terminal 2 of TB-1 if
internal voltage source is used. Tighten
Terminal 2 only at this time.

5. Connect the output side of the switching

circuit to the Channel 1 input negative side
(-) of the opto-coupler at Terminal Block
TB-1, Terminal 4.

a. Normally closed contact of mechanical

switch

b. Normally closed contact of relay contact

c. Open collector output of NPN Transistor

(normally on) for solid-state sensors

d. Collector output of NPN Transistor

(normally on) for PLC interface or
computer card

Tighten Terminal 4 of Terminal Block TB-1
securely.

NOTe: For operation of the CBC-400/CBC-450
to power up with Channel 1 output “on” in
alternate mode or both outputs “off” in
simultaneous mode, the Channel 1 input switch
must be maintained closed for mechanical
switches or “on” in the case of solid-state
switches.

6. Connect the input side of the switching circuit

when mechanical switches are used to the
negative side (-) of the DC power source.

a. External negative (-) of external DC power

source

or,

b. Negative (-) or DC common of the internal DC

power source, Terminal 8 of Terminal Block
TB-1 securely.

7. For external sensors or when using PLC output

modules or computer cards, connect power
source to sensors or cards accordingly.

a. External power source, positive (+) and

negative (-) to appropriate leads on terminals

or,

b. Internal power source, positive (+) Terminal 7,

TB-1 and negative (-) Terminal 8, TB-1 to
appropriate sensor leads of terminals. Tighten
Terminals 7 and 8 securely.

8. Optional Channel 2 Override Input Wiring

NOTe: If using the Channel 2 override input
(start override) the switching circuit must be
a maintained type so that Channel 1 input
switching will have no effect on the output
when maintained.

a. Connect the output side of the switching

circuit to the Channel 2 override input
negative side (-) of the opto-coupler at
Terminal 6 of Terminal Block TB-1.

1. Maintained switch, normally open contact

2. Normally open relay contact

P-239-23 • 819-0500 Warner Electric • 800-825-9050