12 in. ventsafe – Val-Matic 4-12 in. VentSafe Security Cage User Manual

Page 2

Advertising
background image

1

ITEM DESCRIPTION MATERIAL

1

Body

PVC

2

Screen, 20 Mesh 304 Stainless Steel

3

Cage, 2 Mesh

304 Stainless Steel

4-12 in. VentSafe

®

Security Cage

OPERATION, MAINTENANCE AND INSTALLATION


INTRODUCTION

This manual will provide you with the information to
properly install, maintain and ensure a long service
life for the VentSafe

®

. The VentSafe

®

is to be

installed in vent pipes used to vent vaults, reservoirs
and air valves to prevent the entrance of foreign
objects and to provide a barrier against the
intentional introduction of liquids into the vent pipe
(see figure 1).

RECEIVING AND STORAGE

Inspect the VentSafe

®

upon receipt for damage in

shipment. Unload all devices carefully to the ground
without dropping.

The devices should remain boxed, clean and dry
until installed to prevent weather related damage.

DESCRIPTION OF OPERATION

The VentSafe

®

is a wafer-style, screened cage to

deter unauthorized access and to prevent foreign
objects from entering the valve, vault or reservoir
vent, but still allow the vent to perform its function of
admitting and expelling air under normal operating
conditions.

INSTALLATION

The installation of the VentSafe

®

is important for its

proper operation. The VentSafe

®

can be installed in

the vertical or horizontal position between typical
ANSI Class 125 flanges using standard connection
practices. The VentSafe

®

Security Cage can be

located above ground as shown in Figure 2. The
device can also be placed in series at both locations
for added protection. When installed at the end of
the vent pipe a ring-type flange is needed on the end
of the pipe to secure the device in place,

Flanged connections should only be mated with flat-
faced pipe flanges. The bolts should be tightened in
gradual steps using the crossover method.

Recommended torque values are given in Table 1.
The VentSafe

®

can be used with or without flange

gaskets since the vent piping is not pressurized.








TABLE 1. FLANGE BOLT TORQUES



VENTSAFE

®

CONSTRUCTION

The standard VentSafe

®

is constructed of quality

corrosion resistant materials including polyvinyl
chloride (PVC) and stainless steel type 304. The
general details of construction are illustrated in
Figure 1 and identified in Table 2.

Figure 1: VentSafe

®

Cross Section of

Components


Table 2: VentSafe

®

Parts List



Mounting Flange Bolts

Device

Size

Bolt

Size

Recommended

Torque (ft-lbs)

Maximum

Torque (ft-lbs)

4 5/8”

20

30

8 3/4”

30

40

12 7/8"

60

70

CAUTION:

The use of excessive bolt torque
may damage the device.

Advertising