6. Fault Finding

FAULT

REASON

SOLUTION

Air conditioner does
not start

Power supply not or incorrectly connected

Connect the power supply correctly

Temperature in the control cabinet is below
the target value.

Wait until the temperature target value is
exceeded. The air conditioner will start by itself.
If the target value of the control cabinet
temperature is too high set a lower target value

Door contact open

Close the enclosure door or bridge door contact
connections.

Air conditioner doesn’t
cool the air

Compressor faulty

The compressor must be
changed. This process must
be carried out by the
manufacturer.

Compressor protection switch has been
activated

Check cooling capacity. If the cooling capacity is
too low at the operating conditions find another
location with lower ambient temperatures or
install an additional air conditioner

Evaporator and/or condenser are heavily
soiled or blocked

The evaporator and/or compressor must be
cleaned

The cooling output of the air conditioner is
too low for the heat generated by the
components in the control cabinet

Check cooling capacity. If the cooling capacity is
too low at the operating conditions find another
location with lower ambient temperatures or
install an additional air conditioner

Evaporator iced up

Insufficient refrigerant due to refrigerant loss
through leaks in circuit

Refrigerant circuit must be
sealed and refilled. This
process must be carried out
by the manufacturer.

The ambient temperature is far below the
lower operating limit.

Place the air conditioner in an area where the
temperature remains within the operating limits

The enclosure is not sealed

Seal the enclosure

Fan or fan capacitor cold side defective

Replace fan and/or fan capacitor

Heavy condensation

Enclosure door is not completely closed

Close the door

Enclosure is not sealed

Seal the enclosure

Incomplete seal at the contact surfaces
between air conditioner and enclosure

Seal the contact surfaces and stiffen the
mounting surface of the enclosure if necessary

Uneven temperature
distribution in the
control cabinet

Enclosure air intake and outlet blocked or
partially impeded by components inside

Move components or change position of air
conditioner

Enclosure volume too large for air
conditioner

Check cooling capacity. If the cooling capacity is
too low at the operating conditions find another
location with lower ambient temperatures or
install an additional air conditioner

Short circuit of the air

Change the air guidance

Condenser fan does
not run

Fan defective

Replace fan