Technical data, Ambient fans – SEIFERT Variable Speed Air Conditioner KG 2002-24V User Manual

Page 2

Advertising
background image

2 |

I n s t r u c t i o n S h e e t K G - 2 0 0 2

3.

Technical Data

KG-2002

Part- No

20020240

20020480

Housing material/Surface finish

Mild steel, powder coated RAL 7035

Optional: stainless steel, Part-no. 20xx … 2

Housing dimensions

260 x 203.2 x 220 mm

Weight

6.8 kg

Operational temp. range

+10°C ... +55°C

Cooling performance according to DIN 3168 L35 L35

Max. Cooling capacity @ L35L35

480 W

Max Power consumption L35L35

295 W

380 W

Compressor

Speed controlled rotary compressor

Refrigerant

R134a

Refrigerant load

82g

Max. working Pressure

PS 40 / PO 37bar

Maximum air volume flow

Ambient air circuit

280 m

3

/h

Cabinet air circuit

190 m

3

/h

Electrical data

Nominal Voltage

24 V DC

48 V DC

Operating Voltage Range

20 ... 30 V DC

43 ... 60 V DC

Rated current (max)

14.5 A

10.2 A

Power Consumption at max. Conditions

350 W

490 W

The company reserves the right to make technical changes.

4.

Ambient Fans

The ambient fans could be mounted either on the left or right hand side of the unit, depending on the preferred ambient inlet location.

To change the location of the ambient fans:
- Disassemble the main cover, disconnect connectors, and remove blowers from rubber mounting.
- Remove blanking plates, and mount blowers on the other side of the unit.
- Place blanking plates on the other side of the unit.
- Connect connectors, and close main cover.

When changing the location of the ambient blowers always make sure the following:
-Fans are properly assembled to the rubber mounts
-Both fans are blowing in the same direction
-Blanking plates are used in the cut-outs not in use.

For optimum performance it is recommended that the fans are assembled in such a way that the fans are blowing towards the condenser and
not sucking out of the condenser.