HMI5000P Installation Guide

1010-1014 Rev 01 www.maplesystems.com

Figure 3: Power Line Filter Connection

Cable Routing and Noise Immunity

Follow these guidelines when routing cables to the HMI:

Always route the HMI communication cable and the power cable

away from any AC voltage or rapidly switching DC control
lines.

Never bundle the HMI cables together with 120VAC power

wires or with relay wiring.

Try to keep at least 8 inches (20 cm) of separation between the

HMI cables and other power wiring. If voltages greater than
120VAC are used in the system, greater separation is required.

If the HMI cables must come near AC wiring, make sure they

cross at 90 degrees.

Run AC power wires in a separate grounded conduit to reduce

electrical noise interference.

Keep the cable lengths for the HMI as short as possible. Do not

coil excess cable and place it next to AC powered equipment.

Cover any equipment used in the enclosure that operates at high

frequency or high current levels with a grounded metal shield.