General specifications – Proface AGP3300H - 5.7 Handheld HMIs" User Manual

Page 3

Advertising
background image

3

General Specifications

„ Electrical Specifications

„ Environmental Specifications

Po

wer Supp

ly

Input Voltage

DC24V

Rated Voltage

DC19.2 to 28.8V

Allowable

Voltage Drop

2ms (max.)

Power

Consumption

13W (max.)

In-Rush

Current

60A (max.)

*1

*1 The FWHM (Full-width, half maximum) value is approximately 40µs. (When exceeding 30A)

Voltage Endurance

AC1000V 20mA for 1minute (between charging and FG terminals)

Insulation Resistance DC500V 10M

Ω (min.) (between charging and FG terminals)

Phy

s

ic

al

Surrounding Air
Temperature

0 to +50

°C

*1

*1 When using AGP3200-A1-D24 in an environment where the temperature becomes or exceeds 40°C

for an extended period of time, the screen contrast level may decrease from its original level of
brightness.

Storage
Temperature

-20 to +60

°C

Ambient Humidity

10 to 90% RH

(Wet bulb temperature: 39°C max. - no condensation.)

Storage Humidity

10 to 90% RH

(Wet bulb temperature: 39°C max. - no condensation.)

Dust

0.1mg/m

3

and below (non-conductive levels)

Pollution Degree

For use in Pollution Degree 2 environment.

Advertising