Grounding Cautions

• Be sure to create an exclusive ground for

the Power Cord’s FG terminal. Use a
grounding resistance of 100

Ω, a wire of

2mm

2

or thicker, or your country’s applica-

ble standard.

• The SG (signal ground) and FG (frame

ground) terminals are connected internally
in the GP unit.
When connecting the SG line to another
device, be sure that the design of the sys-
tem/connection does not produce a short-
ing loop.

• The grounding wire should have a cross

sectional area greater then 2mm

2

. Create

the connection point as close to the GP unit
as possible, and make the wire as short as
possible. When using a long grounding
wire, replace the thin wire with a thicker
wire, and place it in a duct.

4.

Input/Output Signal Line Cautions

• All GP Input and Output signal lines must

be separated from all operating circuit
(power) cables.

• If this is not possible, use a shielded cable

and ground the shield.

To prevent the USB cable
from coming off

• When using USB Host Interface in

Hazardous Locations, please fix the
USB cable with the USB Holder.

• When using USB Host Interface in

Hazardous Locations, it is necessary
to meet the following requirements.

a) Use the associated USB Cable

Clamp:
CA5-USBATL-01 (made by Pro-face)

b) Use the USB cable with the housing

that suits the associated USB Cable
Clamp:
CA3-USBCB-01 (made by Pro-face)
or USB cable with the housing of the
same size as CA3-USBCB-01
(If USB cable with a small housing is
used, it may not be securely fixed.)

„ Attaching the USB Holder

(1) Before starting the procedure, lift up the

tab on both sides of the USB Holder and
remove the USB Cover.

GP unit

Other
Equipment

Exclusive Grounding

(BEST)

GP unit

Other
Equipment

Common Grounding (OK)

GP unit

Other
Equipment

Common Grounding

(Not OK)