‹ LT3201-A1-D24-C Output Circuit (Source type)

• Since the output terminals are not electrically protected, an output line might be short-cir-

cuited or a connection fault might damage the LT unit. Please install an applicable fuse to pre-

vent an overload in the circuit, if necessary.

„ High-Speed Counter / Pulse Catch Input Specifications

DIO Standard Input/Output is used as a High-Speed Counter Input. The setup is done by the
GP-Pro EX.

GP-Pro EX Reference Manual “Controlling External I/O”

Counter

Pulse Catch

Input

DC24V Open Collector

DC24V Open Collector

Single Phase
(4 points)

2 Phase
(1 point or 2 points)

Input Points

CT0 (IN0),
CT1 (IN2),
CT2 (IN4),
CT3 (IN6)

CT0 (IN0), CT1 (IN2)
(used as pair)
CT0: A Phase,
CT1: B Phase
CT2 (IN4), CT3 (IN6)
(used as pair)
CT2: A Phase,
CT3: B Phase

IN0, IN2,

IN4, IN6

High Speed Count
Frequency

100Kpps

50Kpps

Marker Input
(Counter Value Clear)

None

IN3, IN7

L

L

Internal Circuit

Internal Circuit

Fuse
2.5A

DC 24V
External
Power

+24V B8

0V A8

OUT5 A11

OUT4 B11
OUT3 A10
OUT2 B10
OUT1 A9
OUT0 B9

+
-

Dummy
Resistor

*1

*1 (Example) The output delay time (ON to OFF) is 1.5

µs where the output current is

DC 24V, 50mA. Install an external dummy resistor to increase the amount of
current when more responsiveness is required and the load is light.