Proface APL3000B - Node Box PC User Manual

Page 7

Advertising
background image

7

Serial Mode Select Switches (SW4 to SW10) operate as shown in the circuit diagram below.

5

Switches the TX
termination
resistance ON/
OFF

Inserts
termination
resistance of
220

Ω between

TXA and TXB.

No termination

OFF

ON

ON/
OFF

*2

6

Switches the RX
termination
resistance ON/
OFF

Inserts
termination
resistance of
220

Ω between

RXA and RXB.

No termination

OFF

ON

ON/
OFF

*2

7

Switches the
shorting of TXA
and RXA ON/OFF

Shorts TXA and
RXA
(RS-485 mode)

No shorting
(RS-422 mode)

OFF

OFF

ON

8

Switches the
shorting of TXB
and RXB ON/OFF

Shorts TXB and
RXB
(RS-485 mode)

No shorting
(RS-422 mode)

OFF

OFF

ON

9

RTS Automatic
control mode
(enabled only
when RS-485
mode)

The data is
automatically
controlled via the
RTS signal.

The data is not
automatically
controlled via
the RTS signal.

OFF

OFF

ON/
OFF

*3

10

OFF

OFF

ON/
OFF

*3

Table 2) Serial Mode Select Switches

*1 Be sure to keep the settings, "OFF" for RS-422 or RS-485.

*2 If you use the termination resistance, base your settings on the connection specifications.

*3 To control TX output driver via RTS automatically, set ON. Be sure to set SW No.4 OFF.

Not to control TX output driver via RTS automatically, set OFF. Be sure to set SW No.4 ON.

Switch

No.

Description

ON

OFF

RS-

232C

RS-

422

RS-

485

TXD

RTS

SW4

SW9

SW10

SW5

SW7

SW6

SW8

TXA

TXB

RXA

RXB

RTS Automatic
control

COM2