WATLOW IND.

FIREBAR® Circulation Heater Installation & Maintenance Manual

I&M Number: 316-42-1-1

Page: 3

Date: 06-11-08

Rev: 2.00

________________________________________________________________________________________________________________________________________________________________________________________________________________________

WATLOW IND.n # 6 INDUSTRIAL LOOP RD. n HANNIBAL MO, 63401n PHONE 573-221-2816 n FAX 573-221-3723

INLET

OUTLET

OUTLET

INLET

Preferred Orientation

"TOP" stamped
on flange

"TOP" stamped
on flange

Optional Orientation

Figure # 1

If the tank is installed in any other position, it's important that "TOP" be located on the same side as the
nozzles. This will insure that element supports create a baffling effect, and that flow can easily move
through the element bundle. Unless fluid velocity is high, side orientation of nozzles and elements
are not recommended.


Figure #2 shows the preferred position of the circulation heater when pumping liquif from a tank through
the heater. The NPSH (Net Positive Suction Head) is one of the most important factors when
determining the location of the heater.

NPSH

PUMP

NPSH

PUMP

INCORRECT HEATER POSITION - HEATER ABOVE NPSH

CORRECT HEATER POSITION - HEATER BELOW NPSH

Figure # 2


Furnish adequate space for horizontal or vertical installation. Space should be allowed for immersion
heater removal from tank.