Watlow ind, Start up, Troubleshooting – Watlow WATROD Flange Heater User Manual

Page 4

Advertising
background image

WATLOW IND.

WATROD

Flange Heater Installation & Maintenance Manual

I&M NUMBER: 316-42-8-1

Page: 4

Date:6/11/2008

Rev:

2.00

_________________________________________________________________________________________________________________________________________________________________________________________________________________________
______

WATLOW IND.n # 6 INDUSTRIAL LOOP RD. n HANNIBAL MO, 63401n PHONE 573-221-2816 n FAX 573-221-3723


Line voltage must be equal to or less than rating stamped on the heater assembly. Some units are
supplied as dual voltage . Example: 240V / 480V, check wiring diagram supplied with the unit to make
sure which scheme was used. In most cases (unless specified by customer) units are wired for the
higher voltage.


Thermostats can be supplied with flange heaters. Consult the wiring diagram supplied with the heater
for the suggested wiring of thermostats. For safe operation of thermostats, consult Installation and
Maintenance manual for thermostats that is attached.


Thermostats should not be used as an "OFF" device; the use of a disconnect switch or circuit breaker is
recommended. The disconnect switch will allow isolation of the heater when maintenance of the heater
is required.

Start Up

Before energizing the heater the following items should have been checked with the heater power

disconnected:

1. Immersed section of heater is completely covered by liquid
2. Electrical termination is tight and wiring is per wiring diagram supplied with heater
3. Proper disconnecting means and fusing have been installed
4. The voltage rating of the heater is the same as that being applied
5. Megohm is within acceptable limits
6. Proper temperature controls and safety limiting devices are in place
7. Heater is securely installed in tank header and no leaks are visible

After applying power to the heater make sure that the system is being controlled properly before leaving it to
run unattended. Failure to do this could result in overheating resulting in personnel danger and fire.

Troubleshooting

PROBLEM

Cause / Correction

No power available to heater

Check disconnect switch to ensure it is in the "ON" position

and that fuses are not blown. Replace fuses if they are blown

Fuses blowing

Check heater electrical rating. Applied voltage may be wrong

Check fuse rating. Fuses should be at least 25% more than full
load amperage.
Disconnect heater power source. Check the heater resistance
to ground. This should be no less than 1 Megohm. Refer to
Megohm checking.

Not enough power

Check line voltage to ensure it is within specification

Check full line current if voltage is correct. If line current is lower,
the heater may be wired wrong or has open elements

Fluid not heating to desired

Not enough Kw

temperature

Too much heat loss

High limit tripping / alarm

Not enough fluid flow

Too much Kw

Advertising