Specifications, Analog inputs, Analog inputs thermocouple ranges rtd ranges – Watlow 8LS Controller User Manual

Page 15

Advertising
background image

Introduction

8LS User’s Guide 7

Specifications

Analog Inputs

Thermocouple Ranges

RTD Ranges

Analog inputs

8, solid state, differential

Optical isolation

120 Vac between inputs; 175 Vac from input to ground

A/D converter

Integrating voltage to frequency

DC voltage range

-10 to 60 mV. You can change it with scaling resistors to

any range from 0 to 25V

Resolution

0.02%, greater than 12 bits

Accuracy

0.05% at 25°C

Calibration

Automatic zero and full scale

Temperature coefficient

Less than 50 ppm/C, 0.005%/°C

Normal mode rejection

60 db at 60 Hz, full scale range maximum

Loop update time

2 times per second, every input

T/C burnout

Full upscale reading of input standard

DC milliamp inputs

4-20 mA, 10-50 mA, 0-50 mA, etc., with scaling resistors

Input Range

0-1V, 0-5V, 0-10V, 0-12V, up to 0-25 Vdc, with scaling

resistors

Infrared inputs

Power supply included, with scaling resistors

Source impedance

Measurements are within specification with up to 500

ohms source resistance

J

-350 to 1400°F -212

to

760°C

K

-450 to 2500°F

-268 to 1371°C

T

-450 to 750°F

-268 to 399°C

B

150 to 3200°F

66 to 1760°C

S

0 to 3200°F

-18 to 1760°C

R

0 to 3210°F

-18 to 1766°C

N

-450 to 2370°F

-268 to 1299°C

RTD1

-148.0 to +572.0°F

-100 to 300°C

0.1°

RTD2

-184.0 to +1544.0°F

-120 to 840°C

0.2°

Advertising