Inputs, Inputs 98, Table 7.11— analog inputs 98 – Watlow CAS200 User Manual

Page 110

Advertising
background image

Chapter 7: Specifications

CAS200 User’s Guide

98

Watlow Anafaze

Inputs

The scanner accepts analog sensor inputs which are
measured and may be used as feedback for control loops. It
also accepts digital (TTL) inputs which may be used to
trigger certain firmware features.

Table 7.11

Analog Inputs

Parameter

Description

Number of Channels

17

Number of Analog Inputs

16 with full range of input types, plus one pulse

Input Switching

Single-ended, solid state multiplexer

Input Sampling Rate

1.5Hz (667ms) at 60Hz; 1.25Hz (800ms) at 50Hz

Analog Over Voltage
Protection

±20V referenced to digital ground.

Common Mode
Rejection (CMR)

For inputs that do not exceed

±5V, >60dB dc to 1kHz,

and 120dB at selected line frequency.

A/D Converter

Integrates voltage to frequency

Input Range

-10 to +60mV, or 0 to 25V with
scaling resistors

Resolution

0.006%, greater than 14 bits (internal)

Accuracy

0.03% of full scale (60mV) at 25°C

0.08% of full scale (60mV) at 0-50°C

Calibration

Automatic zero and full scale

Analog Ground to Frame Ground
Maximum

40V

DC Common to Frame Ground
Maximum Potential

40V

Thermocouple Break Detection

Pulse type for upscale break detection

Milliampere Inputs

0-20mA (3

Ω resistance) or 0-10mA (6Ω resistance),

with
scaling resistors

Linear Voltage Input Ranges
Available

0-12V, 0-10V, 0-5V, 0-1V, 0-500mV, 0-100mV with
scaling resistors.

Source Impedance

For 60mV thermocouple, measurements are within
specification with up to 500

Ω source resistance

For other types of analog signals, the maximum source
impedance is 5000

Advertising