Example 3, Situation, Setup – Watlow CAS User Manual

Page 87

Advertising
background image

Appendix: Linear Scaling Examples

CAS User’s Guide 77

Example 3

Situation

A pulse encoder which measures the movement of a conveyor is
connected to the CAS. The encoder generates 900 pulses for every inch
the conveyor moves. You want to measure conveyor speed in feet per
minute (f/m).

Setup

The encoder input is connected to the pulse input. An one second
sample time gives adequate resolution of the conveyor's speed.

The resolution is:

so a display format of -99.99 to +300.00 is appropriate.

The input readings are as follows.

At the maximum pulse rate of the CAS (2000 Hz):

At zero hertz, the input reading will be 0.00 f/m.
Therefore, the scaling values are:

Parameter

Low Value

High Value

Process Value (PV)

0 f/m

1.11 f/m

Input Reading (RDG)

0 Hz

2000 Hz

1 pulse

1

ond

sec

---------------------

60

onds

sec

1minute

---------------------------

1 inch

900pulses

--------------------------

Ч

Ч

1 foot

12inches

-----------------------

×

0.006 f m

=

200pulses

1

ond

sec

--------------------------

60

onds

sec

1minute

---------------------------

1 inch

900pulses

--------------------------

Ч

Ч

1 foot

12inches

-----------------------

×

11.11 f m

=

Advertising