Tb-50 – Watlow CLS User Manual

Page 40

Advertising
background image

32 CLS User’s Guide

Installation

TB-50 Connections

4 and 8 CLS TB-50 Connections.

If you install a Watlow Anafaze Serial Digital to Analog Converter
(SDAC), the CLS uses digital output #34 for a clock line. You cannot
use output #34 for anything else when you have an SDAC installed.

* The indicated outputs are dedicated to PID (or control) when enabled
in the loop setup. If one or both of a loop’s outputs are disabled, the
corresponding digital outputs become available for alarms or ramp/soak
events.

Pin

Function

PID Output*

8CLS 4CLS

Pin

Function

PID Output*

8CLS 4CLS

1

+5 Vdc

2

+5 Vdc

3

CTRL COM

4

CTRL COM

5

Not Used

6

Watchdog Timer

7

Pulse Input

8

Global Alarm

9

DIG output 1

Loop 1 heat

Loop 1 heat

10

DIG output 34*

11

DIG output 2

Loop 2 heat

Loop 2 heat

12

DIG output 33

13

DIG output 3

Loop 3 heat

Loop 3 heat

14

DIG output 32

15

DIG output 4

Loop 4 heat

Loop 4 heat

16

DIG output 31

17

DIG output 5

Loop 5 heat

Pulse loop
heat

18

DIG output 30

19

DIG output 6

Loop 6 heat

Loop 1 cool

20

DIG output 29

21

DIG output 7

Loop 7 heat

Loop 2 cool

22

DIG output 28

23

DIG output 8

Loop 8 heat

Loop 3 cool

24

DIG output 27

25

DIG output 9

Pulse loop
heat

Loop 4 cool

26

DIG output 26

27

DIG output 10

Loop 1 cool

Pulse loop
cool

28

DIG output 25

29

DIG output 11

Loop 2 cool

30

DIG output 24

31

DIG output 12

Loop 3 cool

32

DIG output 23

33

DIG output 13

Loop 4 cool

34

DIG output 22

35

DIG output 14

Loop 5 cool

36

DIG output 21

37

DIG output 15

Loop 6 cool

38

DIG output 20

39

DIG output 16

Loop 7 cool

40

DIG output 19

41

DIG output 17

Loop 8 cool

42

DIG output 18

Pulse loop
cool

43

DIG input 1

44

DIG input 2

45

DIG input 3

46

DIG input 4

47

DIG input 5

48

DIG input 6

49

DIG input 7

50

DIG input 8

Advertising