Communications Baud Rate

Use this menu to set the Communications Baud Rate to 2400 or 9600
baud.

Selectable values:

9600 or 2400.

NOTE

If you use ANASOFT, be sure to set ANAINSTL to

the same baud rate that you set in this menu.

Allen Bradley Protocol

Use this menu to set the protocol type to either Allen Bradley or
ANAFAZE.

Selectable values:

Yes or No.

AC Line Frequency

Use this menu to configure the controller to match an AC line frequency
of 50 or 60 Hz. (This function is provided for international users who
require 50 Hz lines.) Since the controller reduces the effect of power
line noise on the analog measurement by integrating the signal over the
period of the AC line frequency, the controller's noise rejection will
suffer if the line frequency is not set correctly.

Selectable values:

60 Hz or 50 Hz.

NOTE

If you change the AC line frequency, you must switch
power to the MLS on and off for the change to take

effect.