Watlow Power Supply for MLS300 User Manual

Ac - d c, 60 watts, Dnr05-60 series

Advertising
background image

A

C

-

D

C

Specification

5-60 Watts

Rugged Design for Industrial Applications

Up to 89% Efficiency

Wide Adjustment Range

DC OK 24 V Models

DC Standby Versions

Connector Options

Full Power to +60 ˚C

DNR05-60 Series

Input

Input Voltage

• 90-264 VAC, 120-370 VDC: DNR05/10/18

85-264 VAC, 90-375 VDC: DNR30/60

Input Frequency

• 47-63 Hz

Inrush Current

• 5-18 W: 10/18 A at 115/230 VAC

30 W: 20/40 A at 115/230 VAC
60 W: 30/60 A at 115/230 VAC

Power Factor

• Meets EN61000-3-2 for class A equipment

Earth Leakage Current

• 0.8 mA max

Output

Output Voltage

• See tables

Output Voltage Trim

• See tables

Initial Set Accuracy

• ±1%

Minimum Load

• No minimum load required

Start Up Delay

• <1000 ms

Start Up Rise Time

• <150 ms

Hold Up Time

• 5 W: 30/130 ms at 115/230 VAC

10 W: 25/100 ms at 115/230 VAC
18 W: 20/75 ms at 115/230 VAC
30 W: 20/30 ms at 115/230 VAC
60 W: 20/30 ms at 115/230 VAC

Line Regulation

• 5-18 W: ±1.0% max

30-60 W: ±0.5% max

Load Regulation

• 5-18 W: ±2.0% max

30-60 W: ±0.5% max

Transient Response

• 300 µs for a 50% load change

Ripple & Noise

• 50 mV pk-pk, 20 MHz BW

Overvoltage Protection • Output clamps at 120-145% Vnom

Overload Protection

• 105-145%

Short Circuit Protection • 5-18 W: Trip and restart (Hiccup mode)

30-60 W: Constant power

Temperature

• ±0.03%/ºC

Coefficient

xppower.com

General

Efficiency

• See tables

Isolation

• 3000 VAC Input to Output

1500 VAC Input to Ground
500 VAC Output to Ground

Switching Frequency

• 100 KHz typical

Signals

• DC ON indicator LED Green: All models

DC LOW indicator LED Red:
5-18 W models
DC OK: 24 V 30-60 W models

MTBF

• 200 kHrs typical per MIL-HDBK-217F

GF, +40 ºC

Environmental

Operating Temperature • -10 °C to +70 °C, derate linearly from

+50 °C for 5 & 18 W models, +60 °C for
all other models (See derating curves)

Cooling

• Convection-cooled

Operating Humidity

• 20-95% RH, non-condensing

Storage Temperature

• -25 ºC to +85 ºC

Shock

• 4 g, 22 ms, X, Y & Z axis

Vibration

• 1 g, 10 Hz to 500 kHz, along X, Y & Z axis

EMC & Safety

Emissions

• EN55022, level B conducted

Harmonic Currents

• EN61000-3-2, class A

Voltage Flicker

• EN61000-3-3 amendments 1 & 2

ESD Immunity

• EN61000-4-2, level 3 Perf Criteria A

Radiated Immunity

• EN61000-4-3, level 3 Perf Criteria A

EFT/Burst

• EN61000-4-4, level 3 Perf Criteria A

Surge

• EN61000-4-5, level 3 Perf Criteria A

Dips & Interruptions

• EN61000-4-11, 30% 10 ms,

60% 100 ms, 100% 5000 ms
Perf Criteria A, B, B

Safety Approvals

• EN60950-1:2001, UL508,

UL1310 - see note 3 & ratings table,
UL60950-1, cUL60950-1, CE Mark

Advertising