Chapter 2: Install & Wire

Output Wiring

*1 NOTE: A contactor is
required if a high limit
control is used.
*2 NOTE: A separate
disconnect is required
for the fan(s) if used.

QPAC-33 Power and Load
Wiring for
all Units.

Circuit

Breakers

or

Disconnects

Contactors
If Required

3 factory-

supplied

semiconductor

fuses

Heater

Load

Fan 120VÅ (ac)/20W

L1
L2

L1

L2

L3

L1

T1

L2

T2

L3

T3

Hybrid

*1

*2

G

WARNING: Shock Hazard
Heatsinks are electrically
Live.

ç

CAUTION:
Check terminals for
tightness before ap-
plying power and then
recheck terminals after
one day of operation.
Loose connections can
damage the SCR.

NOTE:
A circuit breaker is re-
quired in addition to the
semiconductor fuses.
All semiconductor fuses
are mounted on-board
the QPAC models 400 to
1,000. Where third-leg
fusing is selected, addi-
tional space is required.

NOTE:
QPAC models Q01, Q32
and Q33 up to 300A and
575V

Å

(ac) are agency

listed. QPAC models Q01
and Q32 up to 1,000A
and 480V

Å

(ac) are

agency listed. Q33 400
to 1,000A are not agency
listed.

WARNING:
To avoid damage to
property and equipment,
and/or injury or loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the QPAC.
Failure to do so could
result in damage and/or
injury or death.