Power wiring, Input wiring, Output wiring – Watlow Series 146 User Manual

Page 3: Remote reset

Advertising
background image

120VÅ

146_ - 1 _ _ _ - 0000

230 to 240 VÅ

146_ - 2 _ _ _ - 0000

24VÅ

146_ - 3 _ _ _ - 0000

NOTE: The line voltage is specified by your model number.

ç

WARNING: To avoid potential electric shock, use National

Electrical Code safety practices when wiring and connecting this
unit to a power source and to electrical sensors or peripheral
devices. All wiring and fusing must conform to the National Electric
Code and to any locally applicable codes. Failure to comply with
these recommendations could result in damage to equipment and
property, and injury to personnel.

ç

WARNING: The Series 146 safety limit should be mounted in an

inconspicuous location to discourage unauthorized changes to the
set point. Only approved and appropriate personnel should have the
authority to change the set point on the limit switch. Failure to com-
ply with these recommendations could result in damage to equip-
ment and property, and injury to personnel.

ç

CAUTION: Applying incorrect voltage may result in irreversible

damage to the controller.

Figure 3a — Power wiring.

15

L1

Fuse

L2

1

3

Recommended

fuse size: 1A

Power Disconnect
Switch

Power Wiring

Thermocouple

Figure 3b — Thermocouple wiring.

2- and 3-Wire RTD

Figure 3c — 2- and 3-Wire RTD Wiring

NOTE: 2- or 3-wire RTD input, calibrated for 0.003850

/°C curve.

Electromechanical Relay, Form C

8A

146E - _ _ _ _ - _ 000

ç

Figure 3d — Electromechanical relay wiring.

Figure 3e — Remote reset wiring.

NOTE: The Series 146 used with a
remote reset may affect FM recogni-
tion. Only the use of a momentary
switch is valid for approval.

NOTE: Reset is customer-supplied.

15 16 17

14

13

Customer-Supplied

Reset

Remote Reset

NOTE: Switching induc-
tive loads (relay coils,
solenoids, etc.) with the
mechanical relay,
switched dc or solid-
state relay output
options requires use of
an R.C. Suppressor.
Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part
No. 0804-0147-0000.

15

L1

Fuse

Customer
Supplied
Quencharc

L2

5

NC

External
Device

High
Temperature
Light

NO

7

C

9

Output Wiring

10 11 12

S1

S2

S3

3-wire RTD

10 11

S1

S2

S3

12

2-wire RTD

+ –

10 11

Input Wiring

3

Watlow Series 146 User’s Manual

Advertising