Watlow Series 935A User’s Manual

3 5

Thermocouple and Remote Set Point Input Field Calibration Procedure

Equipment Required:
• Type “J” Reference Compensator with reference junction at 32°F/0°C, or Type “J” Thermocouple Calibrator set at 32°F/0°C.
• Precision millivolt source, 0-50mV min. range, 0.01mV resolution.

Set Up:
1.
Connect 100-240

Å

(ac), or 24-28V

(ac/dc) to Terminal 7 and Terminal 8.

2. Connect the millivolt source to Terminal 1 negative and Terminal 2 positive.
3. Connect voltage source to Terminal 3 negative and Terminal 4 positive.
4. Apply power to the unit and allow it to warm up for 15 minutes.

Move to the Calibration Menu:
1.
Press

.

and

,

simultaneously for 3 seconds.

2. Press

.

or

,

until

[CnFG]

is displayed.

Press and hold

ß

– press

.

or

,

to select

[`YES]

, then release

ß

.

3. Press

.

or

,

until

[`TAG]

is displayed.

Press and hold

ß

. Press

.

or

,

8 times (display shall be blank).

Calibration: (Thermocouple)
1.
Press and hold

ß

,

.

, and

,

simultaneously for 3 seconds until

[TR50]

is displayed.

2. Set the mV source to 50.00mV

Î

(dc). Set the voltage source to 5.00V

Î

(dc). Allow 10 seconds for sources to stabilize. Press and

hold

ß

. Press

.

or

,

until

[`YES]

appears. Release

ß

.

3. Press

,

-

[Tc00]

shall be displayed.

4. Set the mV source to 0.00 mV

Î

(dc), set voltage source to 0.00V

Î

(dc). Allow 10 seconds for sources to stabilize. Press and hold

ß

. Press

.

or

,

until

[`YES]

appears. Release

ß

.

5. Press

,

.

[``Tc]

shall be displayed.

6. Set the MV source to 0.00 mV (if using a temperature compensator). Set calibrator to 32°F/0°C.

Set voltage source to 0.00V. Allow 10 seconds for sources to stabilize.
Press and hold

ß

. Press

.

or

,

until

[`YES]

is displayed. Release

ß

.

Calibration: (RTD)
Equipment Required:
• Precision Resistance Box with 0.01

Resolution.

1. Remove thermocouple wires from Terminal 1 and Terminal 2.
2. Connect S2 to terminal 1. Connect S1 to Terminal 2.
3. Press

,

.

[R`15]

shall be displayed.

4. Connect voltage source to Terminal 3 negative and Terminal 4 positive.
5. Set the Decade box to 15.00

, set the voltage source to 0.00V (Allow 10 seconds for sources to stabilize). Press and hold

ß

.

Press

.

or

,

until

[`YES]

appears. Release

ß

.

6. Press

,

-

[R380]

shall be displayed.

7. Set the decade box to 380.00

, set the voltage source to 5.00V. (Allow 10 seconds for sources to stabilize). Press and hold

ß

.

Press

.

or

,

until

[`YES]

appears. Release

ß

.

8. Press and hold

.

and

,

for 3 seconds to Exit calibration menu.

Calibrating the 935A and Remote Set Point Input