5.16

WATLOW Series 982 User’s Manual

Operation Menus, Chapter 5

Operation-PID

Output 2 Rate

Tune the rate to eliminate overshoot on startup or after the set
point changes.

The rate setting will not influence the percent power if the

process value is more than twice the proportional band from the set point.
When set to [`)00], rate is disabled.

[`rA2] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``US] and [`Pb2] is set higher than [```0].

Default

[`)00]

… [`(99]

min.

[`rA2]

[`rA2]

Output 2 Derivative

Tune the derivative to eliminate overshoot on startup or after the
set point changes.

The derivative setting will not influence the percent

power if the process value is more than twice the proportional band from
the set point. When set to [`)00], derivative is disabled.

[`dE2] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``SI] and [`Pb2] is set higher than [```0].

Default

[`)00] … [`(99]

min.

[`dE2]

[`dE2]

[`dE2]

[`rA2]