Keys and indicator lights, Watlow controls 4 ehg sl10 user’s guide, Dpu] [dpv – Watlow Series EHG SL10 Integrated Temperature Controller User Manual

Page 4: Dbu] [dbv

Advertising
background image

Watlow Controls

4

EHG SL10 User’s Guide

Alarm (flashing red)
Indicates that the process
temperature is higher than the
Limit High Set Point.
Alert (solid red)
Indicates that the process
temperature is higher than the
Closed Loop Set Point plus the

High Temperature Alert
Value

.

Output (green)
Indicates that the output is on.

In Range (solid yellow)
Indicates that the process
temperature is in the normal
operating range (see figure at
right).

Up-Arrow Key

Increases the

displayed value.

Down-Arrow Key

Decreases the

displayed value.

Mode Key

Toggles the display between

the set point and process

temperature. Enters edited

values and advances

to the next prompt.

Optional Communications

Connectors

Flashing
Alert/Alarm
(red) and
In Range (yellow)

If they are flashing together, that
indicates an Ambient Alarm
(controller temperature higher
than 85°C).

If they are flashing alternately, that
indicates a Health Check Error.

Optional Communications

Connectors

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

flashing

flashing

alternate
flashing

Control

relay

LTA

HTA

relay

Safety

Alarm

relay

off off off

off off on

off on on

on on on

off off off Ambient

Alarm

[Abt] 85°C

on off on

off off off Health

Check

Error

Normal Operating Range

Limit High Set Point

[SLA]

Closed Loop Set Point plus
High Temperature Alert
Value

[HtA]

Closed Loop Set Point minus
Low Temperature Alert
Value

[LtA]

T

emper

atur

e

Alarm Hysteresis

Alarm Hysteresis

On-Off Hysteresis

[HyS]

Closed Loop Set Point

Keys and Indicator Lights

Display

Parameter Name & Description

Range

Default

Modbus
Relative

Address

Data Type

& Read/

Write

[dPu]
[dPv]

Display Prototype Version

View the interface’s prototype version.

0 to 9999

- - - -

12

unsigned
integer

R

[dbu]
[dbv]

Display Build Version

View the interface’s build number.

0 to 9999

- - - -

13

unsigned
integer

R

Note:

All values above 999 will be rounded off to fit in the three-character display. Full values can be

read with other interfaces.

Note:

The EHG SL10 does not support Modbus function code 16 (0x10) Write Multiple Registers. Pa-
rameter values must be written individually with function code 6 (0x06) Write Single Registers.

R: Read
W: Write
E: EEPROM