Wa t l o w S e r i e s S D

3 5

C h a p t e r 5 S e t u p

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus in

parenthesis.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[`t;gn]
[ t.gn]

Tune Gain

Select the responsiveness of the
TRU-TUNE+ adaptive tuning
calculations. More responsiveness
may increase overshoot.

1 to 7 Least to most re-

sponsive.

4

354

rw

TRU-TUNE+ version
only. (SD_ E - _ _ _ _ - _
_ _ _ ).

[`LOC]
[ LOC]

Lockout

Set the security level for the
user interface.

[```0] (0) no lockout ***

Full profile access.

[```1] (1) Set Point, Au-

to/Manual, alarms only.
*** Full profile access

[```2] (2) Set Point,

Auto/Manual, only. ***
Pre-Run and Run Menu
access only. View a run-
ning profile. Profile edit-
ing not permitted.

[```3] (3) Set Point only

*** Profile access not
permitted.

[```4] (4) full lockout ***

Profile access not per-
mitted. See the Features
chapter for details.

[```0] (0)

43 R/W

Always active.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).

*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).