Watlow Series SD31 PID with Optional Countdown Timer User Manual

Page 66

Advertising
background image

Wa t l o w S e r i e s S D 3 1

6 4

A p p e n d i x

Electromechanical Relay, Form A

Minimum load current: 10 mA

2 A @ 240V

Å (ac) or 30VÎ (dc) maximum, resistive

125 VA pilot duty, 120/240V

Å (ac), inductive

Must use RC suppression for inductive loads

Electrical life 100,000 cycles at rated current

Process

Range selectable: 0 to 20 mA, 4 to 20 mA, 0 to 5V

Î (dc), 1 to

5V

Î (dc), 0 to 10VÎ (dc)

Reverse or direct acting

0 to 10V

Î (dc) voltage output into 1,000

minimum load resist-

ance

0 to 20 mA current output into 800

maximum load resistance

Resolution:

dc ranges: 2.5 mV nominal

mA ranges: 5 µA nominal

Calibration accuracy:

dc ranges: ±15 mV

mA ranges: ±30 µA

Temperature stability: 100 ppm/°C

Communications

EIA/TIA-485

Isolated

Modbus™ RTU protocol

9600, 19200 and 38400 baud rates

A maximum of 32 units can be connected (with additional 485
repeater hardware, up to 247 units may be connected)

Sampling rate: 20 Hz

Timer Accuracy

± 1 second/hour

Agency Approvals

UL Listed Process Control UL3121

®

(UL 61010C-1), c-UL, CE,

IP65 (NEMA 4X). File # E185611.

UL

®

is a registered trademark of the Underwriter’s Laborato-

ries, Inc.

CSA approved C22.2#24, File 158031

NSF2 approved for type E, J, K, T, and RTD sensors. File 49660-
0002-000

Terminals

Touch-safe

Input power and control outputs: 0.2 to 4 mm

2

(22 to 12 AWG),

6 mm (0.25 in) strip length

Sensor inputs and process outputs: 0.1 to 0.5 mm

2

(28 to 20

AWG), 8 mm (0.30 in) strip length

Solid or tinned wire recommended for spring clamp style con-
nectors.

Torque: terminal blocks 1 to 6 (SD _ _ - _ [C, K or J] _ _ - _ _ _ _)
and 1 to 4 (SD _ _ - _ F _ _ - _ _ _ _ ) are 0.8 Nm (7 in-lb).

Power

100 to 240V

Å (ac) +10%; -15%; 50/60 Hz, ±5%

24V

‡ (ac/dc) +10%; -15%; 50/60 Hz, ±5%; Class 2 power source

is required for low-voltage model.

10VA maximum power consumption

Data retention upon power failure via nonvolatile memory

Operating Environment

-18 to 65°C (0 to 149°F)

0 to 90% RH, non-condensing

Storage temperature: -40 to 85°C (-40 to 185°F)

Dimensions

Height - 29.7 mm (1.17 in)

Width - 52.6 mm (2.07 in)

Behind panel - 97.8 mm (3.85 in

Functionality Matrix

Note: These specifications are subject to change without prior
notice.

Universal

Input

Control

Alarm

Process 485 Comm

Input 1

Output 1

Output 2

Advertising