Mounting height of refrigerant sensors should be within 20 inches of the floor. The Forward of Std. 15-2010 states ,
“(all commonly used refrigerants, except ammonia (R-717)….. are heavier than air).” By placing the sensor below the
common breathing height of 5 to 6 feet, you will provide and added margin of safety.
Floor Plan Location- If ventilation equipment is running continuously, the sensor should be located between the
refrigeration system and room exhaust, as close to the refrigerant equipment as possible. One sensor will usually be
adequate for applications with two (or less) chillers, provided chillers are aligned for good air flow and both chillers use
the same refrigerant. If ventilation equipment is NOT running continuously or if the direction of airflow is not obvious-
locate the sensor(s) next to the refrigeration system. As a general guideline, a refrigeration system should not be more
than 50 feet from a refrigeration sensor.
NOTE: See Toxalert Technical Bulletins- “ToxRefrig InstRec- Section 5 (of the product catalog)”.
The following is a partial list of refrigerants that Toxalert monitors.
TABLE 1
Refrigerant
Name
TLV-
TWA
(a)
PPM
Refrigerant
Name
TLV-
TWA
PPM
Safety Group A1
(b)
R-11
Trichoroflouremethane
1100
R-402A
R-125/290/22
1000
R-12
Dichlorodifluoromethane
18000
R-404A
R-125/143a/134a
1000
R-13
Chlorotrifluoromethane
1000
R-407C
R-32/125/134a
1000
R-13B1
Bromotrifluoromethane
1000
R-410A
R-32/125
1000
R-14
Tetrafluoromethane (Carbon
Tetrafluoride)
1000
R-500
R-12/152a
1000
R-22
Chlorodifluoromethane
1000
R-502
R-22/115
1000
R-113
Trichorotrifluoroethane
1000
R-503
R-23 & R-13
1000
R-114
Dichlorotetrafluoroethane
1000
R-507
R-125 & R-143a
1000
R-115
Chloropentafluoroethane
1000
R-740
Argon
…..
R-134a
1,1,1,2-Tetrafluoroethane
1000
R-744
Carbon Dioxide
5000
Safety Group A2
(b)
R-142b
1-Chloro-1, 1-Diflurorethane
1000
R-152a
1,1-Difluroethane
1000
Safety Group A3
(b)
R-170
Ethane
1000
R-600a
2-Methyl propane
(Isobutane
1000
R-290
Propane
1000
R-1150
Ethene (Ethylene)
200
R-600
Butane
1000
R-1270
Popene (Propylene)
500
Safety Group B1
(b)
R-123
2,2-Dichlor-1, 1,1-Triflurooethane
50
R764
Sulfur Dioxide
…..
Safety Group B2
(b)
R-40
Chloromethane (Methyul
Chloride)
…..
R-717
Ammonia
25
R-611
Methyl Formate
100
(a) threshold limit value time weighted average: the time – weighted average concentration for a normal 8-hour
workday and a 40 hour work week to which nearly all works may be repeatedly exposed, day after day, without
adverse effect (as defined by ACGIH®). TLV® is a trademark of the American Conference of Governmental
Industrial Hygienists (ACGIH®).
(b)
Defined by ANSI/ASHRAE Standard 34-2010
Note – See Toxalert Technical Bulletin Refrig for more information on refrigerant classifications.