UNIT INDICATORS:

Refer to Figure 1.

The Tox-O

2

has five LED’s (light emitting

diodes) to assist in installation and system
diagnostics.

1. Power:

Green LED indicates power to
sensor.

2. Loop Current:

Green LED indicates that the 4 to
20 mA loop is flowing in output
circuit. LED intensity varies with
current flow.

3. Sensor Failure:

Red LED indicates the sensor has
failed.

4. Warning Relay (K1):

Red LED indicates oxygen concen-
tration is below relay setpoint and
relay is energized.

5. Alarm Relay (K2):

Red LED indicates oxygen
concentration is below relay
setpoint and relay is energized.

SPECIFICATIONS

Operating Temperature: 41ºF to 104ºF

(5ºC to 40ºC)

Storage Temperature: -4ºF to 140ºF

(-20ºC to 60ºC)

Relative Humidity: 0 to 95% non-condensing
Relay Output Indicator: Red LED when energized
Output Signal:

Tox-O

2

/1 - Linear 4 to 20 mA Sensor failure 2

mA or less

Tox-O

2

/4 - Warning relay and alarm relay

Mounting style: Surface
Weight: 2 pounds

Type: Electrochemical cell diffusion barrier

oxygen sensor.

Range: 0-25% Oxygen
Response Time: 10 seconds to 90% of change
Sensing Element Life: 10 years in normal service
Accuracy: + / - .75% of Full Scale
Electrical Data:

Input voltage: 24 vdc nominal (8.5 to 26.4 vdc)
Input power: Less than one watt
Loop resistance: 600 ohms maximum
Input current: 25 mA
Wiring: 3 wire non-isolated

Unit Construction:

Housing: Division 1, Class 1, Group B, C & D
Physical: 7”H x 4-1/2” W x 3-3/4” D