Operation: specifications – Toxalert CM203 User Manual

Page 2

Advertising
background image

The Model CM200 series has a two color LED (light-emitting diode) to indicate its operating status.
When the LED is flashing green, operation is normal and unit is not in alarm. When the LED is flashing
red, the unit is sensing CO above its setting. A continuous red or green indicates failure; and LED off
indicates power failure.

Model CM201 is a single stage carbon monoxide monitor with audible alarm. A red LED and audible
alarm activate when the concentration of CO exceeds the factory-set (user-adjustable) level.

Model CM202 is a two stage carbon monoxide monitor with a relay output for each stage. If the CO
concentration rises and stays above the warning stage setpoint (field adjustable) for a delay period of
thirty seconds continuously, the warning relay, amber warning LED, and a three minute minimum on
timer shall activate. The warning stage shall be activated for a minimum of three minutes and then deacti-
vate if the CO concentration is below the warning stage setpoint. Should the CO concentration remain
above the warning stage setpoint for longer than three minutes, the warning stage shall remain activated
until the CO concentration falls below the warning stage setpoint. If the CO concentration should con-
tinue to rise above the alarm stage setpoint (field adjustable) and remain above the alarm setpoint for a
period of ten minutes, then the alarm stage relay and red alarm LED shall activate.

Model CM203 is a two stage carbon monoxide monitor with a warning stage relay and an audible alarm
with silence switch that is activated by the alarm stage. The operation is the same as the Model CM202
except that the audible alarm replaces the alarm relay.

TOXALERT INTERNATIONAL, INC.,

P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960

Visit our website at www. toxalert. com

• Sensor Type: Solid State Metal Oxide

Semiconductor

• Indicators:

Amber LED for Warning
Red LED for Alarm
Flashing Green/Red LED

Power on - Microprocessor

Operating

• Audible Alarm:

Model 201 - Sustained alarm tone for as long

as gas is present

Model 203 - Alarm horn with silence push

button

• Warning Stage Delay: 30 Seconds
• Minimum Fan On Time:

Model 202 - 3 Minutes
Model 203 - 3 Minutes

• Alarm Horn Delay:

Model 201 - 10 Minutes
Model 203 - 10 Minutes

• Range: 0-250 ppm
• Response Time: Less than 30 Seconds
• Input Power: 12 VDC, 300 mA regulated

OPERATION:

SPECIFICATIONS:

• Relay Contracts: 120VAC, 2A resistive
• Factory Setpoints:

Model 201 - Alarm 50 ppm
Model 202 - Warning 50 ppm,

Alarm 100 ppm

Model 203 - Warning 50 ppm,

Alarm 100 ppm

Other Setpoints available

• Maintenance: None other than routine

calibration check

• Operating:

Temperature: 20º F to 122º F

(-29 C to 50C)

Relative Humidity: 5 to 95%

non-condensing

• Enclosure:

Dimensions - 7.5”H x 5”W x 3-3/8”

(19.05 x 12.7 x 8.57 cm)

Weight: - 3 lbs. (1.3 kg)
Type - Nema 12
Finish - Gray Enamel
Material - Steel