Yokogawa EJX115A User Manual

Page 5

Advertising
background image

Supply unit
The supply unit must be certified by a Notified

body as FISCO model and following trapezoidal or

rectangular output characteristic is used.

Uo = 14...17.5 V (I.S. maximum value)
Io based on spark test result or other

assessment,

No specification of Lo and Co is required on the

certificate or label.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

Loop resistance Rc: 15...150 Ω/km

Inductance per unit length Lc: 0.4...1 mH/km

Capacitance per unit length Cc: 45...200 nF/km

Length of spur cable: max. 60 m (IIC and IIB)

Length of trunk cable: max. 1 km (IIC) or 5 km

(IIB)

Terminators
The terminator must be certified by a Notified body

as FISCO model and at each end of the trunk

cable an approved line terminator with the following

parameters is suitable:

R = 90 . . . 102 Ω

C = 0 . . . 2.2 µF. (0.8...1.2 µF is required in

operation)

The resistor must be infallible according to IEC

60079-11.

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.

● Entity Model

Non-Hazardous

Locations

Hazardous Locations

F0206_R03.ai

Terminator

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit and

Safety Barrier

Terminator

Data

U

U

I

I.S. fieldbus system complying with Entity model

I.S. values Power supply-field device:

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

Calculation of max. allowed cable length:

Ccable ≤ Co – ∑Ci – ∑Ci (Terminator)

Lcable ≤ Lo – ∑Li

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.

c. ATEX Flameproof Type
Caution for ATEX flameproof type
Note 1. EJX series pressure transmitters with

optional code /KF21 for potentially

explosive atmospheres:

• No. KEMA 07ATEX0109

• Applicable Standard:

EN 60079-0:2006, EN 60079-1:2004,

EN 61241-0:2006, EN 61241-1:2004

• Type of Protection and Marking Code:

Ex d IIC T6...T4, Ex tD A21 IP6x T85, T100,

T120

• Group: II

• Category: 2G, 2D

• Enclosure: IP66 and IP67

• Ambient Temperature for gas-proof:

–50 to 75°C (T6), –50 to 80°C (T5),

and –50 to 75°C (T4)

• Maximum Process Temperature (Tp.) for

gas-proof:

85°C (T6), 100°C (T5), and 120°C (T4)

• Maximum Surface Temperature for dust-

proof:

T85°C (Tamb.: –40* to 40°C, Tp.: 85°C)

T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)

T120°C (Tamb.: –40* to 80°C, Tp.: 120°C)

* –15°C when /HE is specified.

Note 2. Electrical Data

• Supply voltage: 32 V dc max.

Output current: 15 mA dc

Note 3. Installation

• All wiring shall comply with local installation

requirements.

• The cable entry devices shall be of a certified

flameproof type, suitable for the conditions of

use.

Advertising