<9. General Specifications>

9-2

IM 01C25K01-01E

Working Pressure Limits (Silicone oil)

Maximum Pressure Limits

All capsules 16 MPa (2300 psi)

Minimum Pressure Limit

See graph below

Atmospheric

pressure

-40

(-40)

0

(32)

40

(104)

80

(176)

120

(248)

1(0.14)

2.7(0.38)

10(1.4)

(psi abs)

100(14.5)

Process temperature °C (°F)

Working

pressure

kPa abs

Applicable range

F0901.ai

Figure 9.1

Working Pressure and Process

Temperature

Supply & Load Requirements “◊” (Optional

features or approval codes may affect

electrical requirements.)

With 24 V DC supply, up to a 550 Ω load can be

used. See graph below.

E-10.5

0.0244

(Ω)

Power supply voltage E (V DC)

600

250

R

10.5

16.6

25.2

42

External

load

resistance

Digital

Communication

range

BRAIN and HART

R=

F0902.ai

Figure 9.2

Relationship Between Power Supply

Voltage and External Load Resistance

Supply Voltage

10.5 to 42 V DC for general use and flameproof

type.

10.5 to 32 V DC for lightning protector (Option

code /A).

10.5 to 30 V DC for intrinsically safe, type n or

non-incendive type.

Minimum voltage limited at 16.6 V DC for digital

communications, BRAIN and HART

Load (Output signal code D, E and J)

0 to 1290 Ω for operation

250 to 600 Ω for digital communication

Communication Requirements “◊”

(Safety approvals may affect electrical

requirements.)

BRAIN

Communication Distance

Up to 2 km (1.25 miles) when using CEV

polyethylene-insulated PVC-sheathed cables.

Communication distance varies depending on

type of cable used.
Load Capacitance

0.22 μF or less
Load Inductance

3.3 mH or less
Input Impedance of communicating device

10 kΩ or more at 2.4 kHz.

HART

Communication Distance

Up to 1.5 km (1 mile) when using multiple

twisted pair cables. Communication distance

varies depending on type of cable used.

EMC Conformity Standards

,

EN61326-1 Class A, Table2 (For use in industrial

locations)

EN61326-2-3