<7. Wiring>

7-5

IM 01C25R01-01E

• Magnified view of the RTD connector in the

transmitter's terminal box.

SUPPL

Y

PULSE

CHECK

ALARM

SUPPL

Y

PULSE

CHECK

ALARM

Protection Cap

Connecting Port

F0714.ai

The RTD cable connecting port is covered with

a cap to keep out dust. The cap should not be

removed until you are ready to install the cable.

CAUTION

Input/output signal is non-isolated.

Do not turn on power supply until you complete

all the wiring work.

In the case of electrical connection code 2

(1/2NPT female) or 4 (M20 female).

• Components for the cable gland

The cable gland assembly consists of an entry,

seal, running coupler, and backnut. Confirm that

the seal is attached inside the entry and that the

thread size of the cable gland is the same as

that for the RTD electrical connection.

F0715.ai

1/2NPT Type

M20 Type

Gasket

Entry with Seal

Running

Coupler

Backnut

Entry with Seal

Running

Coupler

Backnut

Procedure
(1) Disassemble the cable gland: loosen the

running coupler to separate the backnut from

the entry.

(2) Remove the protection cap over the transmitter

electrical connection and install the entry on the

electrical connection. Note that a non-hardening

sealant should be applied to the threads for a

1/2 NPT connection and a gasket should be

used for an M20 connection.

Y

L

P

P

U

S

ESL

UP

K

C

E

H

C

M

R

A

L

A

F0716.ai

(3) Pass the RTD cable through the running

coupler and backnut assembly.

F0717.ai

(4) Insert the RTD cable and firmly plug its

connector into the connecting port in the

transmitter's terminal box.

YL

P

P

U

S

ESL

UP

K

C

E

H

C MR

A

L

A

F0718.ai

(5) Align the running coupler on the entry.