<Appendix 8. Advanced Diagnostics>

A8-3

IM 01C25R03-01E

A8.2.1 Blockage Detection

DIAG_LIM

When the parameter based on pressure fluctuation

exceeds the preset value, EJX diagnoses an

impulse line as blockage and gives an alarm. The

threshold values are set to DIAG_LIM [1] to [10] in

the SENSOR Transducer block.
TableA8.2 shows the default values at the factory

setting, which are different according to the model.

NOTE

When ILBD is performed for the first time, use

the default value. If the pressure fluctuation

amplitude is low or a false alarm is often

generated after ILBD is performed, change the

values of DIAG_LIM according to the procedure

described in A8.2.10.

DIAG_LIM

#

Parameter

Threshold value

[1] fdpmax

Threshold to detect “A Blocking” by

using

RATIO_FDP

[2] fdpmin

Threshold to detect “B Blocking” by

using

RATIO_FDP

[3] fsplmax

Threshold to detect “Large

Fluctuation of Low Side” by using

RATIO_FSPL

[4] fsplmin

Threshold to detect “Low Side

Blocking” by using

RATIO_FSPL

[5] fsphmax

Threshold to detect “Large

Fluctuation of High Side” by using

RATIO_FSPH

[6] fsphmin

Threshold to detect “High Side

Blocking” by using

RATIO_FSPH

[7] blkfmax

Threshold to detect “High Side

Blocking” by using

VALUE_BLKF

[8] blkfmin

Threshold to detect “Low Side

Blocking” by using

VALUE_BLKF

[9] dpavgmax

Threshold to detect “Outside

Diagosis Range” by using

VALUE_

DPAVG and to detect “Invalid

Ref xx” by using

REFERENCE_

DPAVG.

[10] dpavgmin

Threshold to detect “Outside

Diagosis Range” by using

VALUE_

DPAVG and to detect “Invalid

Ref xx” by using

REFERENCE_

DPAVG.

Table A8.2 Default Values of DIAG_LIM

#

Parameter

Multivariable transmitter

EJX910A / EJX930A

[1] fdpmax

3

[2] fdpmin

0.3

[3] fsplmax

5

[4] fsplmin

0.5

[5] fsphmax

5

[6] fsphmin

0.5

[7] blkfmax

0.6

[8] blkfmin

-0.6

[9] dpavgmax

*1

1

[10] dpavgmin

*1

0.05

*1:

It indicates the threshold value for “Outside Diagnosis

Range” (refer to A8.2.5).

A/B Blocking Detection

“A Blocking” and “B Blocking” indicates the result

estimated from blockage degree based on the

difference of the high- and low-pressure-side

fluctuation values. RATIO_FDP, SQRT (VALUE_

FDP / REFERENCE_FDP) is used to detect A/B

Blocking.

REFERENCE_FDP is the average value of the sum

of squares of differential pressure fluctuations under

normal condition. As the value of RATIO_FDP

exceeds the value of DIAG_LIM [1], EJX gives

basically an alarm of “A Blocking”. On the other

hand, if this value is below the value of DIAG_LIM

[2], EJX gives an alarm of “B Blocking. As a high- or

low-pressure-side blockage progresses, VALUE_

FDP increases. Therefore, “A Blocking” with a

differential pressure transmitter indicates that a

single-side impulse line is plugged for a differential

pressure transmitter.

As the both-side blockages progress

simultaneously, VALUE_FDP decreases.

Therefore, “B Blocking” with a differential pressure

transmitter indicates that bothside impulse lines are

plugged.

NOTE

A single-side impulse line blockage may

generate “B blocking” under the condition where

the fluctuation amplitude is much different

between high- and low-pressure sides.

With a transmitter to measure pressure or tank

level, “B Blocking” only is detected.