3 view objects, 4 function block parameters, 3 view – Yokogawa digitalYEWFLO (DY-FF) User Manual

Page 24: Objects, Function block parameters -7

Advertising
background image

<5. CONFIGURATION>

5-7

IM 01F06F00-01EN

F0505.ai

AI2 OUT

AI1 OUT

FBOD

Alert

Trend

VCR

DLSAP
DLCEP

Fieldbus Cable

digital YEWFLO

0xF8 0xF3 0xF4 0xF7 0xF9 0x20

0x07

#1

#2

#3 #4 #8 #6

#7 #5

#1

#3

#2

DI2

OUT

DI1

OUT

System
Management
Information
Base (SMIB)

Network
Management
Information
Base (NMIB)

Resource

block

Transducer

block

Link object

Host 1

Host 2

Device

Figure 5.5

Example of Default Confi guration

5.6.3 View

Objects

View objects are used to group parameters.
This reduces the load of data transactions. Each
digitalYEWFLO supports four view objects for each
of the Resource block, Transducer block, three AI
blocks, two DI blocks, one IT block, one AR block,
and PID block (option /LC1). Each view object
contains a group of the parameters listed in Tables
5.11 to 5.17.

Table 5.10

Purpose of Each View Object

Description

VIEW_1

Set of dynamic parameters required by operator for
plant operation. (PV, SV, OUT, Mode etc.)

VIEW_2

Set of static parameters which need to be shown to
plant operator at once. (Range etc.)

VIEW_3

Set of all the dynamic parameters.

VIEW_4

Set of static parameters for confi guration or
maintenance.

5.6.4 Function Block Parameters

Function block parameters can be read from the
host or can be set. For details of the function blocks,
refer to APPENDIX.