3. OPERATION

IM 01C50T01-01E

3-10

(2) Changing the range while applying an

actual input – Apply values –

This feature allows the lower and upper range
values to be setup automatically with the actual
input applied.

YTA:
WARN-Loop should be
removed from
automatic control

HELP

SAVE

ABORT

OK

1

YTA :
Set the:
1 4mA
2 20mA
3 Exit

HELP

SEND

ABORT

ENTER

2

1. Device setup

2. Diag/Service

3. Calibration

1. Apply values

YTA :
Apply new 4ma input

HELP

SEND

ABORT

OK

3

YTA :
Current applied
process value:50.10 degC
1 Set as 4mA value
2 Read new value
3 Leave as found

HELP

SEND

ABORT

ENTER

4

YTA :
Set the:
1 4mA
2 20mA
3 Exit

HELP

SEND

ABORT

ENTER

5

4

3

Press

OK[F4]

to make the control

loop manual.

Call up “

Apply Values

” display.

To set the lower range value, select

1. 4mA

” and press

ENTER[F4]

.

Apply the input which corresponds
to 4mA. After obtaining stable input,
press

OK[F4]

.

Select “

2. 20mA

” and press

ENTER[F4]

. Apply the value which

corresponding to 20mA and enter it
as URV. (Refer to procedures
and .)

After completing the range change,
select “

3.Exit

” and press

ENTER[F4]

.

The LRV to be changed is 50.10
degC.

• Selecting item 1 sets LRV to

50.10degC.

• Selecting item 2 reads LRV

again.

To set LRV to “

50.10

”, select item 1

and press

ENTER[F4]

.

3.4.5 Damping Time Constant

Setting the response time of each Process Variable to
make it vary slowly with a rapid change in input. Set
the value from 0 to 99 seconds.

If the time constant is set to 2 seconds, Transmitter
calculates a reading every cycle time using the damp-
ing equation, to make the output 63 percent of the
input range after 2 seconds.

This damping time constant is normally set to work
when the temperature makes a step change within 2
percent of the output range. The damping can be
changed using the “PV damp point” parameter .

YTA :
PV Unit&Damp
1 PV Unit degC
2 PV Damp 2 s
3 PV damp point 2 %

HELP

SAVE

HOME

ENTER

1

YTA :
Snsr1 damp
2 s
5

HELP

SAVE

ABORT

ENTER

2

1. Device setup

1. Process variables

2. Variable setting

Unit & Damp

1. PV Unit&Damp

YTA :
PV Unit&Damp
1 PV Unit degC
2 PV Damp 5 s
3 PV damp point 2 %

HELP

SEND

HOME

ENTER

3

SEND

Example: To set the damping time constant for PV to “

5

seconds.

Enter “

2

” to call up “

PV damp

display.

Enter new value, and press

ENTER[F4]

.

Press

SEND[F2]

to send the

setting to the transmitter.
Check that disappears.

# When necessary, change the

setting of “PV damp point”.

Call up “

PV Unit&Damp

” display.