Yokogawa 212 Heat Calculator User Manual

Page 47

Advertising
background image

Parameter

Value

Description

4. UNITS

SI
US

Metric units.
US units.

5.

ENERGY

Set energy units for display.

6. VOLUM

Set volume units for display.

7.

POWER

Set power units for display.

8. FLOW

Set flow rate units for display.

9. FACTOR

xxx.x p/ltr

The K-factor of the flowmeter which has

been programmed. (See flowmeter
manufacturers data.)

10.

CUTOFF

x.xx Hz

Low frequency cut-off of the flowmeter,
expressed in Hz. The Model 212 will
not register flow if the input frequency is
below this value. Note that the default is
0.25Hz and it is recommended to not
change this value unless the flowmeter
produces very low frequencies. (See
Section 3.4.)

11. OFFSET

x.x
YES

0.0
NO

The offset between temperature sensors.
(See Section 3.5).

The offset function is disabled.

12. FM

LOC

Feed
Ret

Location of the flowmeter as being in
either the feed or return line.

Set-up Mode 45