Yokogawa Touch Screen GP20 User Manual

Page 335

Advertising
background image

4-15

IM 04L51B01-01EN

Using Modbus Functions (Communicating with Modbus devices)

1

2

3

4

5

App

4.5.4

Input Registers (Shared with the Modbus server/slave function)

Common Items

• The client device can only read the input registers.

• Decimal place and unit are not included. Specify them on the client device.

• Due to the different number of channels between modules, unavailable channel numbers

will exist. This will not cause a register read error, so you can read the data continuously.

• The register values for unavailable channel numbers are set to 0, and the status

information is set to SKIP.

• Channel range by model

Channel type

GX20/GP20

GX10/GP10

I/O channel

0001 to 0950

0001 to 0250

Math channel

A001 to A100

A001 to A050

I/O Channel Data
• 32-bit Signed Integer

I/O Channel Data

Input Register

Data Type

Lower bytes of the channel 0001 data

300001

32-bit signed integer

Higher bytes of the channel 0001 data

300002

|

|

Lower bytes of the channel 0050 data

300099

Higher bytes of the channel 0050 data

300100

Lower bytes of the channel 0101 data

300101

Higher bytes of the channel 0101 data

300102

|

|

Lower bytes of the channel 0150 data

300199

Higher bytes of the channel 0150 data

300200

Lower bytes of the channel 0201 data

300201

Higher bytes of the channel 0201 data

300202

|

|

Lower bytes of the channel 0250 data

300299

Higher bytes of the channel 0250 data

300300

Lower bytes of the channel 0301 data

300301

Higher bytes of the channel 0301 data

300302

|

|

Lower bytes of the channel 0350 data

300399

Higher bytes of the channel 0350 data

300400

Lower bytes of the channel 0401 data

300401

Higher bytes of the channel 0401 data

300402

|

|

Lower bytes of the channel 0450 data

300499

Higher bytes of the channel 0450 data

300500

Lower bytes of the channel 0501 data

300501

Higher bytes of the channel 0501 data

300502

|

|

Lower bytes of the channel 0550 data

300599

Higher bytes of the channel 0550 data

300600

Lower bytes of the channel 0601 data

300601

Higher bytes of the channel 0601 data

300602

|

|

Lower bytes of the channel 0650 data

300699

Higher bytes of the channel 0650 data

300700

Lower bytes of the channel 0701 data

300701

Higher bytes of the channel 0701 data

300702

|

|

Lower bytes of the channel 0750 data

300799

Higher bytes of the channel 0750 data

300800

Lower bytes of the channel 0801 data

300801

Higher bytes of the channel 0801 data

300802

|

|

Lower bytes of the channel 0850 data

300899

Higher bytes of the channel 0850 data

300900

Continued on next page

4.5 Modbus Function and Register Assignments