Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 31

Advertising
background image

4-4

SM 04L31A01-01E

6 .

Insert the relay into the socket by hand, with the line on the top of the

relay facing to the left.

This line faces left

7 .

Close the back lid of the terminal block.

8 .

Check the angle of the terminal block, install it on the main unit, and then

fasten by tightening the terminal block attachment screws.

9 .

Install the terminal cover, and fasten with the terminal cover screws.

1 0 . Confirm that the instrument functions properly, then perform a

withstanding voltage test on the contact output terminal to protective

ground of each control relay.

4.1 Replacement of the Control Output Terminal Block (Module)