Yokogawa Button Operated MV2000 User Manual

Page 92

Advertising
background image

3-18

M-4660

3.10 Counting Pulses (/PM1 option)

• Example 1: Pulse Sum

Display the sum of the pulses from pulse input terminal 6.

Number of pulses

per scan interval

TLOG.SUM

Pulse sum value

Pulse input

Scan interval

Time

(Sum)

P6

Calculation Expression

Select the channel and set the calculation expression. Set an appropriate Span

Lower, Span Upper, and Unit.

Channel

Calculation Expression

Description

101

TLOG.SUM(P6)

The sum of the number of pulses in each scan
interval.

• Example 2: Pulses Per Minute

Using the RD-MV2008 (scan interval 250 ms), count the number of pulses received by

pulse input terminal 6, and calculate the number of pulses per minute.

Number of pulses

per second

101ch

102ch

Number of pulses

per minute

Pulse input

Sampling interval

(250 ms)

Time

(Moving average over a minute)

(60x)

Calculation Expression

This table shows which calculation expressions to assign to which channels. Set an

appropriate Span Lower, Span Upper, and Unit.

Channel

Calculation Expression

Description

101

Q6

Number of pulses per second

102

101*K01

Number of pulses per minute

Constant

Value

Description

K01

60

The coefficient for converting pulses per
second to pulses per minute.

Channel

Rolling Average

Description

101

Interval: 1 s

Moving average over a minute

Number of samples: 60

Channel

Computation starts with the smallest channel number at every scan interval.
Assign larger channel numbers to computation channels that calculate pulses per

minute than you assign to computation channels that calculate pulses per second.

Advertising