8. SETTING ALARM-RELATED PARAMETERS

8.1

Setting Ranges and Factory-Set Values of Alarm-Related Parameters

The followings are the factory-set values for the range code No. 1.
They may differ depending on the range code No. specified at the time of order.

Alarm Action Type Code

Low-limit
alarm
setpoint

Power ON

PV

Time

Normal

Regarded

as normal

Abnormal

(Alarm ON)

If an alarm type code with
stand-by action is set, alarm
action is turned off during the
start-up control.
This function is useful at power
ON or when changing the alarm
type.

Stand-by Action

Parameter Name

Setting Range

Factory-Set

Value

Parameter

Symbol

2

Alarm-1 action
(AL1)

Within the instrument input range.

Setting range: 0 to 999 sec.
Setting resolution: 1 sec.

Setting range: 0 to 999 sec.
Setting resolution: 1 sec.

See the Alarm Action Type Codes table.

Alarm-2 action
(AL2)

1

Alarm-3 action
(AL3)

1

3

Alarm-4 action
(AL4)

Alamr-1 hysteresis
(HY1)

The value resulting from adding a hysteresis value

to an alarm setpoint should be within the
instrument input range.

Within the instrument input range.

3

Alarm-2 hysteresis
(HY2)

3

Alarm-3 hysteresis
(HY3)

3

Alarm-4 hysteresis
(HY4)

0

Alarm ON delay
(OND)

0

Alarm OFF delay
(OFD)

Minimum

value of the

instrument

input range

Setpoint
(SP)

Parameter Name

Setting Range

Factory-Set

Value

Parameter

Symbol

20

2 points of alarms: 80
4 points of alarms: 30

2 points of alarms: 1
4 points of alarms: 2

70

80

Setup Parameter Screen 1

Operation Parameter Screen

Deviation

low-limit

alarm

Deviation

high-limit

alarm

Deviation

high and
low-limit

alarm

Deviation

within high

and low-limit

alarm

PV high-limit

alarm

PV low-limit

alarm

De-
energized
under
Normal
Condition

(Parameters A1 to A4 are not displayed.)

Without Stand-by

Action

With Stand-by

Action

De-
energized
under
Normal
Condition

Energized
under
Normal
Condition

Energized
under
Normal
Condition

Hysteresis

Alarm

Alarm setpoint

Normal

PV

PV

PV

PV

PV

PV

Hysteresis

Normal

Alarm setpoint

Alarm

Hysteresis

Hysteresis

Hysteresis

Alarm

Setpoint

Deviation setpoint

Normal

Hysteresis

Hysteresis

Hysteresis

Normal

Setpoint

Deviation setpoint

Setpoint

Deviation setpoint

Deviation setpoint

Setpoint

Deviation setpoint

Deviation setpoint

Alarm

Alarm

Normal

Alarm

Alarm

Normal

Normal

Alarm Type

No alarm

Alarm Action

<Alarm Action Type Codes>

Alarm-1 setpoint
(A1)


Alarm-2 setpoint
(A2)


Alarm-3 setpoint
(A3)


Alarm-4 setpoint
(A4)

8.2

Setting Alarm Output-Related Parameters

This section describes an example of setting the alarm-1 action (AL1) to “12” (PV low-limit alarm,
with stand-by action), alarm-1 setpoint (A1) to “0” (

°

C), alarm-1 hysteresis (HY1) to “5” (

°

C), alarm

ON delay (OND) to “5” (sec.) and alarm OFF delay (OFD) to “5” (sec.) with the range code No. (IN)
set to “2” (-60.0 to 600.0

°

C). (Parameters relating to alarm 2 to alarm 4 can be set in the same way

as the procedure below.)

Press or

to display "12."

When the SET/ENT key is pressed for more than 3 sec.
with the Operation Parameter Screen displayed, the Setup
Parameter Screen 1 appears with parameter "AL1"
displayed.

When the power is turned on, the PV screen of the
Operation Parameter Screen appears.

Press the UP or DOWN key to display "5.0" (

°

C) on the

DATA display.

Press the SET/ENT key to accept alarm-1 hysteresis "5.0"
(

°

C).

Press the SET/ENT key to display parameter "OND."

Press for more

than 3 sec.

Press .

This completes the process for
setting the alarm-1 hysteresis.

This completes the process for
setting the alarm-1 action.

This completes the process for
setting the alarm-1 setpoint.

The decimal point blinks during
data change.

Press the UP or DOWN key to display "5" (sec.) on the
DATA display.

Press the SET/ENT key to accept alarm ON delay "5"
(sec).

Press the SET/ENT key again to display parameter
"OFD."

The decimal point blinks during
data change.

The decimal point blinks during
data change.

The decimal point blinks during
data change.

Press the UP or DOWN key to display "5" (sec.) on the
DATA display.

Press the SET/ENT key to accept alarm OFF delay "5"
(sec).

Press the SET/ENT key for more than 3 sec.
This causes the Operation Parameter Screen to appear.

This completes the process for
setting the alarm OFF delay.

The decimal point blinks during
data change.

Press the UP or DOWN key to display "12" on the DATA
display.

Press the SET/ENT key to accept alarm-1 action "12."

Then to set the alarm setpoint, press the SET/ENT key for
more than 3 sec. to display the Operation Parameter
Screen. (To set the hysteresis parameter and successive
settings, press the SET/ENT key to display the next
parameter.)

Setup Parameter Screen 1

Setup Parameter Screen 1

Operation Parameter Screen

Press the SET/ENT key to display parameter "A1."

Press the UP or DOWN key to display a low-limit alarm
value "0.0" (

°

C) that is set to the DATA display.

Press the SET/ENT key to accept low-limit alarm "0.0"
(

°

C).

Operation Parameter Screen

To the Operation Parameter Screen

Power ON

Step 2

Setting the alarm action

Setting the alarm setpoint

Setting the hysteresis

Setting the alarm ON delay

Setting the alarm OFF delay

Press this key for
more than 3 sec.

Press to display "A1."

Press or

to display "0.0."

Press .

Press to

display "OND."

Press .

Press or

to display "5.0."

Press or

to display "5."

Press .

Press .

Press or

to display "5."

Press .

Press for more

than 3 sec.

This completes the process for
setting the alarm ON delay.

9. INPUT ADJUSTMENTS

9.1

Setting Ranges and Factory-Set Values of Adjustment-Related Parameters

Setup Parameter Screen 2

OFF (0) or ON (1)
(This parameter is used (set to ON) to reset adjusted values.)

Ϯ

10% of the instrument input range span (and BL < BH)

Ϯ

10% of the instrument input range span (and AL < AH)

Ϯ

10% of the instrument input range span (and BL < BH)

Ϯ

10% of the instrument input range span (and AL < AH)

Parameter Name

Setting Range

Factory-Set

Value

Parameter

Symbol

OFF

Minimum value of

the instrument

input range

Minimum value of

the instrument

input range

Maximum value of

the instrument

input range

Maximum value of

the instrument

input range

Input adjustment reset
(RST)

Input adjustment point
LOW (BL)

Input adjustment
LOW (AL)

Input adjustment point
HIGH (BH)

Input adjustment
HIGH (AH)