Installation, Operating and Maintenance Instructions for

THERMOLEC electric heaters - type FC & SC - (or tubular FT & ST).

1- Mechanical Installation of THERMOLEC heaters.

1.1 Handling. 1. Remove the shipping covers just before installation.

2. Inspect the heater carefully and report any damage to the manufacturer.

DO NOT INSTALL A DAMAGED HEATER.

1.2 Installation.

Heater Position

1.2.1

The axis of the duct must always be perpendicular to the face of the heater.

1.2.2
1.2.3

The heating elements must always be installed horizontally.

Model SC or ST (Slip-in type)

(Please see drawings page 4).

1.2.4

Cut an opening in the side of the duct.

1.2.5

Slip the heater into the duct until the hole is completely covered by flanges around the heater.

1.2.6

Fasten the heater to the duct with sheet metal screws and seal openings with a suitable sealing compound.

1.2.7

If the heater is heavy, use additional hangers to support the heater.

Model FC or FT (Flanged type)

(Please see drawings page 4).

1.2.8

Flange both ends of the duct outwards on three sides to match the heater’s flanges.

1.2.9

Fasten the heater to the duct with sheet metal screws. (For heavy heaters, use nuts and bolts and additional

hangers to support the heater).

1.2.10

Seal openings with a suitable sealing compound.

1.2.11 Spacing Requirements to obtain Optimal Operating Conditions

(Please see drawings page 4).

24 inches between the heater and filter frames.

** inches between the heater and elbows in the duct.

** inches between the heater and branches in the duct.

** inches between the heater and sharp transitions of the duct.

** = minimum distance = the largest of two dimensions (

W or H) up to 48”.

Examples:

heater of 12” x 12”

minimum distance 12”.

heater

of

30”

x

12” minimum

distance

30”.

Heater

of

60”

x

30” minimum

distance

48”.

48 inches between the heater and a double outlet fan, except with split duct design.

30 inches between the heater and access doors or diffusers, except if a metal screen is supplied with the

heater.

1 inch between the duct at the outlet side and combustible materials for a length of 72”, for vertical ducts only.

For the flanged type, 24 inches between the control box cover and obstructions to allow space for installation and

service.

For the slip-in type, width of the duct (dimension W) + depth of the control box + ten (10) inches between

the control box cover and obstructions to allow slipping the heater out the duct and to allow safe servicing.

2060 rue Lucien-Thimens,
Montréal, Québec, Canada H4R 1L1

The air direction may be either vertical or horizontal, but when the unit is installed horizontally, the cut-out cover
must be on top.

Advertising
This manual is related to the following products: