Acu-steam humidistat, version a – Thermolec AcuSteam User Manual

Page 2

Advertising
background image

ACU-STEAM HUMIDISTAT, version A

Features

 State of Art digital RH sensor

 ROOM or DUCT mounting

 Reprogrammable Microcontroller

 Potentiometer Set-point setting

 Out-door temperature sensor for Set-point Reset

 Green (ON/OFF) and Red (warning) status LEDs

Specifi cations

Set-point range. . . . . . . . . . . . . . . 20% to 50% Relative Humidity
Accuracy. . . . . . . . . . . . . . . . . . . . ±4.5%, without calibration
Linearity . . . . . . . . . . . . . . . . . . . . ±1% in the Set-point range

Differential % RH. . . . . . . . . . . . . ±2%
Outdoor Temp. Reset Range

between -9 ˚F (-23 ˚C) to 27 ˚F (-3 ˚C)

Outdoor reset Temperature vs. Set point change
28

˚F (-2 ˚C) and warmer

No change

27

˚F (-3 ˚C) to 23 ˚F (-5 ˚C) 42%

max,

22

˚F (-6 ˚C) to 18 ˚F (-8 ˚C) 38%

max,

17

˚F (-9 ˚C) to 12 ˚F (-11 ˚C)

34%

max,

11

˚F (-12 ˚C) to 5 ˚F (-15 ˚C)

30%

max,

4

˚F (-16 ˚C) to -2 ˚F (-19 ˚C)

26%

max,

-3

˚F (-20 ˚C) to -9 ˚F (-23 ˚C)

22%

max,

-9

˚F (-23˚C) and colder

20% max.

NOTE: these ranges can vary by ±2 %.

The Outdoor Temperature sets the maximum set point of RH internally.
If the Dial position is higher, the actual set point will be limited as above.

Advertising