background image

RTI Technologies, Inc.

September 15, 1997

Page 10

Figure 4 Hose Evacuation

HOSE EVACUATION

It's important that Air not be introduced into the A/C System during a Charging
procedure. If a Vacuum procedure was performed previously, the following
Hose Evacuation Procedure is not required. If the service valves on the hoses
have been open, the following procedure must be performed:

To Evacuate Hoses, refer to Figure 4 and follow these steps:

1. Close Red and Blue Hose Valves.

2. Open High and Low Gauge Valves.

3. Press top (ON) of rocker switch marked RECOVER/RECYCLE.

4. Let the TC640 run until a vacuum is seen on the Low Side Gauge.

5. Turn High and Low Gauge Valves to OFF.

6. Press bottom (OFF) of rocker switch marked RECOVER/RECYCLE. All Air has

now been removed from the Hoses.

7. Vent any Non-condensable Gas as described in the previous section.