MOUNT BACKBOX TO WALL (Refer to Fig. 1)
1. Remove appliance heater assembly from back box and set aside.
2.

Mount back box in desired location (wall mount only) using the four #10
x 1-1/2” screws and anchors (provided). Drill a 1/4” diameter pilot hole
for plastic anchors at spacing in Fig. 1.

3. Attach conduit hub to a 3/4” NPT nipple and conduit seal fitting to the back

box, top and bottom.

Note: A conduit seal fitting must be used on both top and bottom
conduit entries as close to the unit as possible. Use conduit seal Crouse-
Hinds 3/4” EYSX 21 or equivalent. Conduit should be installed according
to applicable NEC and local codes.

4. Pull wiring into back box.

Note: High Voltage (110 or 240 VAC) wiring must enter thru bottom
conduit and low voltage and
signaling wires must enter thru
top conduit and remain separated
per NFPA 70, NEC, and local codes.

HIGH VOLTAGE WIRING (Refer to Fig. 2)
5. Connect high voltage: Make sure

110 or 240 VAC power is “OFF”.
Refer to high voltage schematic
diagram on page 6.

110 VAC

240 VAC

Pin 6

AC HOT

L-1

Pin 5

Neutral

L-2

Pin 4

Ground

Ground

4

STI-1229HTR Installation Instructions

3/4 in.(25mm) NPT NIPPLE
(NOT PROVIDED)

ENCLOSED BACKBOX

HEATER ASSEMBLY

HIGH VOLTAGE TERMINAL BLOCK

SCREW #8-32 x 3/8 in.

(4) PROVIDED

STROBE APPLIANCE

GASKET (1) PROVIDED

SOLID CLEAR COVER

WASHER (6) PROVIDED

#8-32 x 3/4 in. SOCKET

CAP SCREW (6) PROVIDED

LOW VOLTAGE

ELECTRICAL ENTRY

1/4 in. (6.3mm)

DIA. HOLE

ANCHOR

(4) PROVIDED

SCREW #10 x 1 1/2 in.

(4) PROVIDED

LOW VOLTAGE TERMINAL BLOCK

3/4 in. NPT. NIPPLE

(NOT PROVIDED)

HIGH VOLTAGE

ELECTRICAL ENTRY

APPLIANCE

WIRE

3/4 in. NPT HUB (2) PROVIDED

FIGURE 3

1

HEATER ASSEMBLY

HEATER

OVERTEMP SAFETY
THERMOSTAT

HIGH VOLTAGE
TERMINAL BLOCK

PIN 6

PIN 5

PIN 4

2 A FUSE

CONTROL THERMOSTAT

F

1

2

3

4

5

6

1

2

FIGURE 1

FIGURE 2