VOLTAGE LEVEL ACTIVATION HOOKUP

WHEN THE ALARM OUTPUT VOLTAGE IS RELAY DRIVEN, YOU MUST ADD A 1K RESISTOR

ACROSS ALARM OUTPUT TERMINALS. HOOK UP DIALER AS SHOWN BELOW.

PP-1

STANDBY

BATTERY

(optional)

ALARM CONTROL PANEL

W/VOLTAGE TRIGGER

ALARM OUTPUT

12VDC

+

-

ALARM

+

-

INSTALL 1K OHM
RESISTOR HERE IF
ALARM OUTPUT IS
RELAY DRIVEN

1K

Make sure unit is set to “OFF” prior
to wiring and phone line hook-up.

Match the power cables colored wires to the corresponding
outputs on the alarm panel. Do the same for the telephone
cable.

RED

BLACK

YELLOW

WHITE

RED

GREEN

TEL LINE

Alarm when voltage goes
from 0 to +V (5 to 28Vmax).
Program for N.C. operation.

Alarm when voltage goes
from +V (5 to 28Vmax) to 0.
Program for N.O. operation.

Note: You may either program for momentary or
continuous voltage activation. In continuous mode, make
sure that the alarm condition is maintained for minimum 7
minutes to allow all numbers to be dialed. Pressing the M
button immediately resets the dialer.