General operation, 1 alarm inputs, 1 temperature sensors #1 ,#2 and #3 – Hired-Hand Emergency Back-Up and Alarms: Secondary Sensing System User Manual

Page 17: 2 auxiliary inputs #1, #2, and control system, 3 power out, 2 alarm outputs, 1 siren

Advertising
background image

Manual No. 4801- 2997 Rev 7-08

Secondary Sensing System

17 of 40

7. General

Operation

7.1 Alarm

Inputs

The S

3

has seven inputs that can be used to sound an alarm; Three from temperature sensors, three

auxiliaries, and one for power out. The temperature sensors can be enabled or disabled. If a sensor is
enabled it will be used to generate an alarm. If a sensor is disabled, it will not generate an alarm, even if
the S

3

determines that its readings are out of limits. The Auxiliary and Power Out inputs are always

enabled. The seven alarm inputs are:

7.1.1 Temperature Sensors #1 ,#2 and #3

The S

3

comes from the factory with three temperature sensors. The S

3

will trigger an alarm if the

temperature goes above the high limit setpoint or below the low limit setpoint of the sensors. The S

3

will

wait 30 seconds after a sensor indicates it is out of range before triggering an alarm.

7.1.2 Auxiliary Inputs #1, #2, and Control System

The S

3

is equipped with three auxiliary inputs. These inputs are connected in a closed loop circuit. On the

circuit board located on the door of the alarm enclosure there is a terminal block for connecting the
Auxiliary Inputs (See Section 12.8 for a connection diagram). Each of the connections has an IN and OUT
terminal. If, at any time, the connection between the IN and OUT positions is broken (opened), the alarm
will sound. There are many devices on the market that could be used with these inputs. For instance,
water pressure switches, light meters, and thermostats could all be used. The S

3

will wait 30 seconds after

an auxiliary input is broken before triggering an alarm.

7.1.3 Power

Out

The Power Out alarm indicates that there has been no AC electricity present on the alarm power feed for at
least 30 seconds.

AC Power Fuse:
If it is found that there is power present at the electrical outlet and the Power Alarm is ON at the S

3

, the 3

Amp slow-blow fuse located on the S

3

circuit board (Fuse F1) should be checked for a blown fuse. To

replace a fuse, disconnect AC power, disconnect the positive (+) battery terminal from the battery,
carefully replace the blown fuse with the correctly sized replacement fuse, reconnect the positive (+)
battery terminal to the battery, reapply AC power, and verify the power alarm has cleared. The S

3

will wait

60 seconds after a Power Out indication before triggering an alarm. Refer to the S

3

Circuit Board Layout

in Section 12.2 and Fuse Replacement in Section 9.4.

Terminal Connections to the Battery:
If AC power is out or disconnected from the S

3

AND none of the S

3

Displays or LED’s are ON, verify that

the Battery Positive (+) and Battery Negative (-) quick-connect terminals are securely attached to the
battery. Refer to the S

3

Wiring in Section 12.2.


If the AC power is OFF for an extended period of time with the alarms ON, the Back-Up Battery will
eventually be drained of all power. Refer to Section 9 for additional troubleshooting information.

7.2 Alarm

Outputs

The S

3

has two alarm outputs. These can be used individually or simultaneously. The alarm outputs are:

7.2.1 Siren

The siren hookup to the S

3

will deliver a 12 volt DC signal with a current up to 1.0 amps. Many operators

want to mount the siren a long distance from the controller. Sometimes, this is desirable in order to locate
the siren closer to their dwelling, sometimes to get it away from their animals. The use of a small gauge
wire to connect the Alert Alarm to the siren could cause a great deal of voltage drop. This voltage drop, in
turn, can cause the siren to become inoperative. If the operator wants to mount the siren more than 50 feet
from the controller, a relay with a 12VDC rated coil should be used to switch current to the siren. When a
relay is added, the operator must provide a separate battery and charger for the siren circuit.

Advertising
This manual is related to the following products: