American Power Conversion 750VA User Manual

Page 10

Advertising
background image

8

3: U

SER

C

ONFIGURABLE

I

TEMS

N

OTE

: S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE OR OPTIONAL

S

MART

S

LOT

ACCESSORY CARDS

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Automatic Self-Test

Every 14 days
(336 hours)

Every 7 days
(168 hours),
On Startup Only, No
Self-Test

This function sets the interval
at which the UPS will execute
a self-test. Refer to your soft-
ware manual for details.

UPS ID

UPS_IDEN

Up to eight characters to
define the UPS

Use this field to uniquely
identify the UPS, (ie. server
name or location) for network
management purposes.

Date of Last Battery Re-
placement

Manufacture
Date

Date of Battery Replace-
ment

mm/dd/yy

Reset this date when you
replace the battery module.

Minimum Capacity Before
Return from Shutdown

0 percent

15, 30, 45, 50, 60, 75, 90
percent

The UPS will charge its bat-
teries to the specified percent-
age before return from a shut-
down.

Voltage Sensitivity

The UPS detects and reacts
to line voltage distortions
by transferring to battery
operation to protect the
connected equipment.
Where power quality is
poor, the UPS may fre-
quently transfer to battery
operation. If the connected
equipment can operate
normally under such condi-
tions, reduce the sensitivity
setting to conserve battery
capacity and service life.

Brightly lit: UPS is set to
high sensitivity.

Dimly lit: UPS is set to
medium sensitivity.

Off: UPS is set to
low sensitivity.

To change the UPS sensitiv-
ity, press the voltage sensitiv-
ity
button

(rear panel).

Use a pointed object (such as
a pen) to do so.

You can change the sensitiv-
ity level through PowerChute
software.

Alarm Control

Enable

Mute, Disable

User can mute a present ongo-
ing alarm or disable all exist-
ing alarms permanently.

Shutdown Delay

90 seconds

0, 180, 270, 360, 450,
540, 630 seconds

Sets the interval between the
time when the UPS receives a
shutdown command and ac-
tual shutdown.