The current rating of any plug used with the system
must be at least equal to the current load through the
associated receptacles (see tables below).

Do not

attempt to connect power receptacles in parallel.

* Maximum current draw from each 115V GFCI Duplex

receptacle is 20 amps.

115/230 Volt Dual Voltage Receptacle

The 115/230 volt receptacle can supply up to 35 amps
of 230 volt power to a two wire circuit or up to 35
amps of 115 volt power from each side of a three wire
circuit (up to 70 amps total). Do Not connect the 115
volt circuits in parallel. Current sensing for the auto-
matic idle feature is only in one leg of the three wire
circuit as shown below.

Motor Starting

Most 1.5 HP motors can be started if there is no load
on the motor or other load connected to the machine,

Load from

115/230V

Dual Voltage Receptacle

0

1.1 KW
3.4 KW
5.7 KW
8.0 KW

Each 115V Duplex

20
20
20
20

0

Total from Both

115V Duplexes

40
40
40
20

0

K1616-1 Ranger 8 LPG

Maximum Current Draw - No Welding

Load from

115/230V

Dual Voltage Receptacle

0

1.1 KW
4.5 KW
5.7 KW
8.0 KW

Each 115V

Duplex

20
20
20
20

0

Total from Both

115V Duplexes

40*
40*
40*
20*

0

K1616-1 Ranger 8 LPG

Maximum Current Draw - No Welding - Machines with GFCI Kits

(Receptacle viewed from front of machine)

* Current Sensing for Automatic Idle

230V

115V*

115V

GND

since the full load current rating of a 1.5 HP motor is
approximately 20 amperes (10 amperes for 230 volt
motors). Larger motors through 2 hp can be run pro-
vided the receptacle rating as previously stated is not
exceeded. This may necessitate 230V operation only.

Auxiliary Power While Welding

It must be noted that the above auxiliary power ratings
are with no welding load. Simultaneous welding and
power loads are permitted by following Table I. The
permissible currents shown assume that current is
being drawn from either the 115V or 230V supply (not
both at the same time).

NOTE: Voltage and permissible watts decrease as
“CONTROL” is adjusted to settings less than 10. It is
recommended that at settings less than 10, only
incandescent lighting loads be connected to the auxil-
iary power receptacles.

Standby Power Connections

The Ranger 8 is suitable for temporary, standby, or
emergency power using the engine manufacturer’s
recommended maintenance schedule.

The Ranger 8 can be permanently installed as a
standby power unit for 230V-3 wire, single phase 35
ampere service.

(Connections must be made by a licensed electri-
cian who can determine how the 115/230V power
can be adapted to the particular installation and
comply with all applicable electrical codes.) The
following information can be used as a guide by
the electrician for most applications (refer also to
the connection diagram shown in Figure 1.)

TABLE I

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

Setting

Watts (Unity Power

Current in Amperes

Factor)

@ 115V -or- @ 230V

Max. Stick or Wire

Feed Setting

None

0

0

175 Stick Setting

2100

18

9

125 Stick Setting

3800

32

16

90 Stick Setting

5000

42

21

70 Stick Setting

5600

48

24

50 Stick Setting

6300

54

27

NO WELDING

8000

70

35