Specifications, Options – Schaefer Series CI User Manual

Page 2

Advertising
background image

www.schaeferpower.de

Inverters

1 or 3-Phase Output from 200VA to 45kVA, switchmode

DC / AC Inverters, AC / AC Frequency Converters & Static Switches

Sine Wave

Continuous short circuit protection

Thermal shutdown with auto-restart for

1-phase inverters >1.2kVA

3-phase inverters >3.6kVA

Suitable for complex load

Surge power capability

Industrial grade components

Compact and robust design

3-phase output: Unsymmetrical load permissible,

modular system with interchangeable inverters

Input voltage: 10-800V DC or

115/ 230V AC, single phase, 47-400Hz or

200/ 400/ 480V AC, three phase, 47-400Hz

Output voltage: 115/ 230 V AC, single phase

or 200/ 400/ 480V AC, three phases

Output frequency: 50/ 60/ 400/ 800Hz

(crystal stabilized) or programmable within

40-400Hz or 400-800Hz

Output power: 200VA - 45kVA

Features

Specifications

AC

or

DC

AC

Input

Voltage range

unit switches off at under- and
overvoltage

No-load input power

10 – 30 W

Inrush current

for AC input and DC input >160V:
limited by thermistor

Hold-up time

AC input: 10 ms typical
Series CI: 20ms typical

Immunity

acc. to EN 61000-6-2

General

Efficiency

80 – 92 %

Operating temperature

– 20 to + 75°C
optional: -40 to +75°C

Load derating

2.5%/°C above + 55°C

Storage temperature

-40 to + 85°C

Cooling
(details see page 131)

= natural convection

= incl. temperature controlled fans

Humidity

up to 95 % RH, non-condensing

Safety / Construction

acc. to EN 60950-1 / EN 50178

Protection category

IP20 acc. to EN 60529,
NEMA or others upon request

EMI

acc. to EN 61000-6-4,
class A, optionally class B

MTBF @40°C acc. to
MIL -HDBK-217E (notice1)

series IT:

120.000h

series CI:

70.000h

series IV:

50.000h

Output

Output voltages

115V AC

230V AC

3x200VAC 3x400VAC 3x480VAC

or any other

Output power

from 200 VA up to 45k VA

Line regulation (±10%)

0.1 % for series CI,
2 % for series IT and IV
3 % for series IT and IV @ 400Hz

Load regulation (10-90%)

1 % typical, 3 % max.
(400 Hz: 3 % typical, 5 % max.)

Turn-on rise time

soft-start, 100ms typical

Waveform

sine wave or any wave shape pro-
grammable by external signal

Frequency

40 – 800 Hz: adjustable or
programmable or any fixed
frequency (crystal stabilized)

Distortion

3 % typical, 5 % @ 400 Hz,
7 % @ 40 – 400 Hz, 800Hz

Overload protection
(steady state)

current limited to approx. 1.05 x
nominal current

Surge power

2 x nominal power for 1 s

Short circuit protection

electronically limited to 3 x no-
minal current, unit switches off
after 1 s

Crest factor

approx. 3

Power factor

cos 0.7 inductive / capacitive

Options

Input

Inrush current limiting for DC input

Reverse polarity protection for DC input

Autoranging for 115 / 230 VAC input

Special circuit for 16.6Hz AC input

Output

Remote on / off (inhibit)

Static Switch (details see page 97)

Parallel operation for redundancy or increased power:

series IT5xxx

Signals
via relay contacts

Power ok (input)

AC ok (output)

Monitoring
of input / output voltage, current or frequency via

analog signal

interface card RS232 or CAN Bus (external)

Programming
of output voltage, current or frequency via

potentiometer

analog signal

interface card RS232 or CAN Bus (external)

Mechanics / environment:

19” sub-rack for eurocassette, refer to page 121

Wall mount

Increased mechanical strength

Tropical protection

Extended temperature range to –40 °C

Temperature controlled fans for 19” units

Advertising