Converters from 5 to 40kw, switchmode, Specifications, Options (details see page 115) – Schaefer Series C/B 5300 User Manual

Page 2

Advertising
background image

www.schaeferpower.de

Converters from 5 to 40kW, switchmode

Converters from 5 to 40kW, switchmode

High Power

DC / DC Converters, AC / DC Power Supplies & Battery Chargers

DC Input voltage: from 80 - 800V DC

AC Input voltage: 115 / 230V AC, single phase or

200 / 400 / 480V AC, three phases

AC Input frequency: 47 - 400Hz

Output voltage: 5 / ... / 800V DC

Output current: up to 800A

Output power: 5 - 40kW

Specifications

AC

or

DC

DC

Input / Output isolation

Continuous short circuit protection

Overvoltage protection

Thermal shutdown with auto-restart

Operational from – 40 to +75 °C

Industrial grade components

High efficiency through ZVS topology

High power density

Compact and robust design

Fan or liquid cooled

Features

Input

Voltage range

narrowing of input voltage range
optimizes the efficiency (pls.
specify); unit switches off at
under- and overvoltage

No-load input power

30W typical

Switch-on time

<1s typical

Inrush current

3-phase AC input: limited by
thermistor (except for

series 55

xx,

64xx, 66xx, 67xx & CW/BW56xx)

Immunity

acc. to EN 61000-6-2

Output

DC output voltages

5

9

12

15

24

28

48

60 110 200 220 400 600 800

Output power

from 5 to 40kW

Line regulation (±10%)

0.1%

Load regulation (10-90%)

0.2%

Load transient (10-90-10%) 6 % typical

Response time to ±1 %

10 ms typical

Turn-on rise time

Soft-start, 300 ms typical

Ripple

≤ 1% + 30 mV p-p

Overload protection

current limited to 105-110% of I

nom

Overvoltage protection

OVP switches off module with
automatic return to operation;
after 5 seconds, the unit will
remain latched off

Remote sense

standard for all series up to 150 V
output, except for battery chargers;
up to 10 % of U

nom

for output < 60

VDC, up to 6 V for output > 60 VDC

General

Efficiency

80 - 95% typical

Operating temperature

-20 to +75°C optional: -40 to +75°C

Load derating

2.5%/°C above + 55°C

Storage temperature

-40 to + 85°C

Cooling
(details see page 131)

= fan cooled
= liquid cooled

Humidity

up to 95 % RH, non-condensing

Temperature coefficient

0.02 % / °C typical

Safety / Construction

acc. to EN 60950-1 / EN 50178

Protection category
(built-in module)

IP20 acc. to EN 60529,
NEMA or others upon request

EMI

acc. to EN 61000-6-4,
class A, optionally class B

MTBF

approx. 70,000h @ 40°C
acc. to MIL - HDBK - 217E (notice 1)

Connectors
(details see page 132)

terminals / bolts / bars
or CombiTacs for Series 5100

Options (details see page 115)

Input

Inrush current limiting

Reverse polarity protection for DC input

Output

Decoupling diode for redundant / parallel operation

Active current sharing for parallel operation

Remote on / off (inhibit)

Reducing of current limiting at high ambient temperature

Signals
via relay contacts

Power ok (input)

DC ok (output)

Monitoring
of input / output voltage or current via

analog signal

interface card RS232 or CAN Bus

Programming
of output voltage or current via

potentiometer

analog signal

interface card RS232 or CAN Bus

Programming of battery chargers

Temperature compensated charging voltage

Automatic / manual selection of charging characteristic

Mechanics / environment:

Wall mount

Digital or analog V- and A-meter

Increased mechanical strength

Tropical protection

Extended temperature range to –40 °C